Design of main protection configuration scheme for Zhexi 250 MW hydraulic generator
Different stator winding types of multi-branch generator lead to different internal short circuit fault aggregation, and the main protection scheme research must base on this fault aggregation to decide the optimized branch grouping style on neutral side and the main protection configuration princip...
Saved in:
Published in | Dianli Xitong Baohu yu Kongzhi Vol. 37; no. 22; p. 61 |
---|---|
Main Authors | , |
Format | Journal Article |
Language | Chinese |
Published |
16.11.2008
|
Online Access | Get full text |
Cover
Loading…
Summary: | Different stator winding types of multi-branch generator lead to different internal short circuit fault aggregation, and the main protection scheme research must base on this fault aggregation to decide the optimized branch grouping style on neutral side and the main protection configuration principles. The paper analyzes the stator winding type and internal short circuit faults of 250MW generator in Zhexi hydraulic power station, based on the transient fault simulation results and their protection effects under different main protection schemes, to decide the optimized main protection scheme of this generator. The design process provides a reference for relevant research and engineering application work. |
---|---|
Bibliography: | ObjectType-Article-2 SourceType-Scholarly Journals-1 content type line 23 ObjectType-Feature-1 |
ISSN: | 1674-3415 |