Spatiotemporal modeling of node temperatures in supercomputers

Los Alamos National Laboratory (LANL) is home to many large supercomputing clusters. These clusters require an enormous amount of power (~500-2000 kW each), and most of this energy is converted into heat. Thus, cooling the components of the supercomputer becomes a critical and expensive endeavor. Re...

Full description

Saved in:
Bibliographic Details
Published inJournal of the American Statistical Association
Main Authors Storlie, Curtis Byron, Reich, Brian James, Rust, William Newton, Ticknor, Lawrence O., Bonnie, Amanda Marie, Montoya, Andrew J., Michalak, Sarah E.
Format Journal Article
LanguageEnglish
Published United States Taylor & Francis 10.06.2016
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:Los Alamos National Laboratory (LANL) is home to many large supercomputing clusters. These clusters require an enormous amount of power (~500-2000 kW each), and most of this energy is converted into heat. Thus, cooling the components of the supercomputer becomes a critical and expensive endeavor. Recently a project was initiated to investigate the effect that changes to the cooling system in a machine room had on three large machines that were housed there. Coupled with this goal was the aim to develop a general good-practice for characterizing the effect of cooling changes and monitoring machine node temperatures in this and other machine rooms. This paper focuses on the statistical approach used to quantify the effect that several cooling changes to the room had on the temperatures of the individual nodes of the computers. The largest cluster in the room has 1,600 nodes that run a variety of jobs during general use. Since extremes temperatures are important, a Normal distribution plus generalized Pareto distribution for the upper tail is used to model the marginal distribution, along with a Gaussian process copula to account for spatio-temporal dependence. A Gaussian Markov random field (GMRF) model is used to model the spatial effects on the node temperatures as the cooling changes take place. This model is then used to assess the condition of the node temperatures after each change to the room. The analysis approach was used to uncover the cause of a problematic episode of overheating nodes on one of the supercomputing clusters. Lastly, this same approach can easily be applied to monitor and investigate cooling systems at other data centers, as well.
Bibliography:LA-UR-15-22229
AC52-06NA25396
USDOE
ISSN:0162-1459