Testing the Efficiency of a Heat Pump with Radiant Systems in Heating Mode

The paper deals with the experimental testing of the efficiency of the operation of an air/water heat pump in connection with three radiant systems in heating mode in an office building, which is part of the central laboratories of the Slovak university of Technology in Bratislava. The testing was a...

Full description

Saved in:
Bibliographic Details
Published inPeriodica polytechnica. Mechanical engineering - Mas̆inostroenie
Main Authors Šimko, Martin, Petráš, Dušan, Szabó, Daniel, Živner, Lukáš, Takács, Ján
Format Journal Article
LanguageEnglish
Published 22.10.2024
Online AccessGet full text

Cover

Loading…
More Information
Summary:The paper deals with the experimental testing of the efficiency of the operation of an air/water heat pump in connection with three radiant systems in heating mode in an office building, which is part of the central laboratories of the Slovak university of Technology in Bratislava. The testing was aimed at verifying the manufacturer's theoretical claims about efficiency of the heat pump based on the COP and SCOP values according to EN 14511-1:2022 and EN 14825:2022. The testing period was from 7 Jan. 2024 until 15 Jan. 2024. The aim of the testing measurements was to evaluate the calculated value of SPF efficiency for individual days and for the testing period. During the measuring period, the wall radiant system consumed 188 kWh, the ceiling system 216 kWh, and the floor radiant system 196 kWh. The heat pump consumed 227 kWh of electricity. The calculated SPF value was 2.64.
ISSN:0324-6051
1587-379X
DOI:10.3311/PPme.36791