ANALISIS EFISIENSI TRAFO FAKULTAS TEKNIK UDAYANA BUKIT JIMBARAN DENGAN PENGOPERASIAN FILTER AKTIF BERBASIS FLC

Disruption to the transfomator can result in losses that disrupt the flow of electricity toconsumers. Harmonics are disturbances that arise due to the operation of non-linearloads. The purpose of this study is to analyze the efficiency of the KA4214 transformerat the Udayana Bukit Jimbaran Engineeri...

Full description

Saved in:
Bibliographic Details
Published inJurnal SPEKTRUM Vol. 8; no. 2; p. 178
Main Authors Triya Adi Septiawan, I N., Rinas, I W., Suartika, I M.
Format Journal Article
LanguageEnglish
Published 12.07.2021
Online AccessGet full text

Cover

Loading…
More Information
Summary:Disruption to the transfomator can result in losses that disrupt the flow of electricity toconsumers. Harmonics are disturbances that arise due to the operation of non-linearloads. The purpose of this study is to analyze the efficiency of the KA4214 transformerat the Udayana Bukit Jimbaran Engineering Faculty with harmonics, namely the R =16.9%, S = 13.8% and, T = 16.1%. . The method used is to simulate and analyze withthe results of harmonic measurements in existing conditions, active filters, and activefilters based on fuzzy logic controller using Matlab software. The optimal resultsobtained are using the fuzzy logic controller method with the results of R = 0.85% S =0.65% T = 0.39% and the efficiency results are 99.99%.
ISSN:2302-3163
2684-9186
DOI:10.24843/SPEKTRUM.2021.v08.i02.p20