IDENTIFICATION OF THE BREAKDOWN AND ANALYSIS OF TRANSFORMER 22/0.4 KV

The paper deals with the identification of the breakdown of the transformer withdrawn from operation because of repeated reaction of transformer protections. Successively the transformer was put of operation, removed from the distribution and put to diagnostic measmements. For identification of the...

Full description

Saved in:
Bibliographic Details
Published inMateriálové inžinierstvo Vol. 20; no. 4; p. 195
Main Authors Brandt, Martin, Faktorová, Dagmar, Seewald, Róbert
Format Journal Article
LanguageEnglish
Published Zilina University of Zilina, Faculty of Mechanical Engineering 01.10.2013
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:The paper deals with the identification of the breakdown of the transformer withdrawn from operation because of repeated reaction of transformer protections. Successively the transformer was put of operation, removed from the distribution and put to diagnostic measmements. For identification of the failure were used diagnostic methods, e.g. Sweep Frequency Response Analysis (according to IEC 60076-18), measurement of winding resistances, measmement of isolation resistances and capacitances. The results were compared with reference measmements. [PUBLICATION ABSTRACT]
Bibliography:ObjectType-Article-2
SourceType-Scholarly Journals-1
ObjectType-Feature-1
content type line 23
ISSN:1335-0803
1338-6174