도서관 전열교환기의 재실자수에 따른 기준 환기량 산정 및 수요기반제어

Purpose: Although ERV (Energy Recovery Ventilator) is operating during open hours all the time, students tend to be least satisfied with the indoor air quality of library. This discomfort is getting apparently observed while more students have seated longer time. This study aims to measure whether t...

Full description

Saved in:
Bibliographic Details
Published inKIEAE Journal Vol. 19; no. 2; pp. 87 - 92
Main Authors 윤정욱(Jung-Wook Yoon), 김선혜(Sean-Hay Kim)
Format Journal Article
LanguageKorean
Published 한국생태환경건축학회 01.04.2019
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:Purpose: Although ERV (Energy Recovery Ventilator) is operating during open hours all the time, students tend to be least satisfied with the indoor air quality of library. This discomfort is getting apparently observed while more students have seated longer time. This study aims to measure whether the supplied airflow rate per capita is sufficient against the law-enforced CO2 concentration - 1,500 ppm in an actual university library. Also this study aims to perform a pilot test of the DCV (Demand Controlled Ventilation) based on number of occupants, as a compensation for the increased airflow rate that could be a recommended reaction after through measuring currently supplied airflow rates. Method: We first have fixed the supplied airflow rates while letting go off entering and leaving students as many as the number of students who usually visit the library, and then measured the marginal number of students at each flowrate, which makes CO2 concentration under 1,500 ppm. Also we have fixed the 35 students and then measured the desired airflow rate that maintain CO2 concentration under 1,500 ppm. Lastly, we have tested the occupant-based DCV for the ERV following combinations of the marginal number of students and the desired airflow rates. Result: It is observed that 1) more occupants require larger airflow rates, as expected. It should be noted that when occupants more than a certain number stay in the library, CO2 concentration is increasing faster than it would do when there is smaller number of occupants; 2) when library is pretty much occupied, the law-enforced ventilation rate per capita may not be sufficient to meet CO2 concentration under 1,500 ppm; 3) the occupant-based DCV well contains CO2 concentration under 1,500 ppm upon varied number of occupants, while saving surplus airflow volumes and thus saving the electricity. KCI Citation Count: 0
Bibliography:http://dx.doi.org/10.12813/kieae.2019.19.2.087
ISSN:2288-968X
2288-9698
DOI:10.12813/kieae.2019.19.2.087