전위강하법에 의한 접지저항 측정시 보조전극의 위치변화에 따른 오차 분석
This paper presents numerical analysis of measurement errors of ground electrode using the fall-of-potential method. In order to analyze ground resistance error according to the positions of auxiliary probes, firstly, national and international standards were researched. Secondly, numerical ground r...
Saved in:
Published in | 전기학회 논문지 P권, 59(2) Vol. 59; no. 2; pp. 222 - 231 |
---|---|
Main Authors | , , , , , |
Format | Journal Article |
Language | Korean |
Published |
대한전기학회
2010
|
Subjects | |
Online Access | Get full text |
ISSN | 1229-800X 2586-7792 |
Cover
Loading…
Summary: | This paper presents numerical analysis of measurement errors of ground electrode using the fall-of-potential method. In order to analyze ground resistance error according to the positions of auxiliary probes, firstly, national and international standards were researched. Secondly, numerical ground resistance error of hemispheric electrode was analyzed according to the locations of auxiliary probes and the angle between probes. Then, error-reduced positions of auxiliary probes were shown according to the distance to auxiliary current probe versus ground electrode size. Finally, error compensation method was presented. The results presented in this paper provide useful information regarding ground resistance error of alternative positions of auxiliary probes in case that the auxiliary probes could not be located at the proper position in such cases as there are buildings, roadblock or underground metallic pipe at that position. |
---|---|
Bibliography: | KISTI1.1003/JNL.JAKO201028454239428 G704-001568.2010.59.2.002 |