노말노난올의 연소특성치 측정에 의한 위험성 평가

For the safe handling of n-nonanol, this study was investigated the explosion limits of n-nonanol in the reference data. The flash points and AITs (autoignition temperatures) by ignition delay time were experimented. As a results, the lower and upper explosion limits of n-nonanol recommended 0.8 Vol...

Full description

Saved in:
Bibliographic Details
Published in한국화재소방학회 논문지 Vol. 26; no. 2; pp. 84 - 89
Main Author 하동명(Ha, Dong-Myeong)
Format Journal Article
LanguageKorean
Published 한국화재소방학회 30.04.2012
Subjects
Online AccessGet full text
ISSN1738-7167
2508-6804
2765-088X

Cover

More Information
Summary:For the safe handling of n-nonanol, this study was investigated the explosion limits of n-nonanol in the reference data. The flash points and AITs (autoignition temperatures) by ignition delay time were experimented. As a results, the lower and upper explosion limits of n-nonanol recommended 0.8 Vol.% and 6.1 Vol.%, respectively. The lower flash points of n-nonanol by using closed-cup tester were experimented $94{\sim}97^{\circ}C$. The lower flash points of n-nonanol by using open cup tester were experimented $103{\sim}104^{\circ}C$. This study measured relationship between the AITs and the ignition delay times by using ASTM E659-78 apparatus for n-nonanol. The experimental AIT of n-nonanol was $270^{\circ}C$. 노말노난올의 안전한 취급을 위해, 폭발한계는 문헌을 통해 고찰하였고, 인화점과 발화지연시간에 의한 발화온도를 측정하였다. 그 결과, 노말노난올의 폭발하한계는 0.80 Vol.%, 상한계는 6.1 Vol.%를 추천하였고, 하부인화점은 밀폐계에서 $94{\sim}97^{\circ}C$와 개방식에서 $103{\sim}104^{\circ}C$로 측정되었다. ASTM E659-78 장치를 사용하여 자연발화온도와 발화지연시간을 측정하였고, 노말노난올의 최소자연발화온도는 $270^{\circ}C$로 측정되었다.
Bibliography:KISTI1.1003/JNL.JAKO201218553920728
G704-000951.2012.26.2.003
ISSN:1738-7167
2508-6804
2765-088X