정온전선의 화재 위험성에 관한 연구

This study examines the physical characteristics of self-regulating heating cables caused by increased temperature and fire risk due to local degradation. A thermo hygrostat system, a convection dryer, a digital multimeter (Agilent 34465 A), NI DAQ, and the LabVIEW program were used to assess the ph...

Full description

Saved in:
Bibliographic Details
Published in한국안전학회지 Vol. 39; no. 3; pp. 7 - 13
Main Authors 이정현, Jung Hyun Lee, 김시현, Si Hyun Kim, 박예진, Ye Jin Park, 강신동, Sin Dong Kang, 김재호, Jae-ho Kim
Format Journal Article
LanguageKorean
Published 한국안전학회 30.06.2024
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:This study examines the physical characteristics of self-regulating heating cables caused by increased temperature and fire risk due to local degradation. A thermo hygrostat system, a convection dryer, a digital multimeter (Agilent 34465 A), NI DAQ, and the LabVIEW program were used to assess the physical properties in response to temperature fluctuations. As the temperature increases, the resistance of the self-regulating heating cable increases; however, when the critical point is exceeded, the resistance sharply decreases. A problem arises when the resistance value cannot return to its original state even though the temperature is lowered to the initial state. Moreover, when the ambient temperature rises while power is applied, the resistance value initially increases, and the flowing current decreases, maintaining a constant state. However, when the critical temperature is exceeded, the flowing current increases because of a rapid decrease in the resistance value, progressing to ignition. When the resistance value decreases because of the deterioration of one local area, the total resistance value becomes less than the initial resistance value. Therefore, the flowing current increases and an ignition problem occurs at one location where deterioration occurs. Despite the sustained flames and arcs resulting from the changes in the overall physical properties of the self-regulating heating cable and resistance variations due to local decline, the fire continued as the flowing current was lower than the operating current of the circuit breaker, failing to cut the power. In the case of self-regulating heating cables and heating wires, which are the leading causes of fires in winter, efforts are needed to ensure the need for periodic maintenance and the use of KS-certified products.
Bibliography:Korean Society of Safety
KISTI1.1003/JNL.JAKO202426457687863
ISSN:1738-3803
2383-9953