Research on circuit breaker lightning failure of open-ring point in 220kV electromagnetic loop network

A typical circuit breaker lightning fault of open-ring point in 220kV electromagnetic loop network is analyzed. The lightning intruding into the fracture of circuit breaker causes total internal reflection. And it's the main reason causing the damage of circuit breakers in recent years. Through...

Full description

Saved in:
Bibliographic Details
Published in2014 International Conference on Lightning Protection (ICLP) pp. 269 - 272
Main Authors Manling Dong, Huan Ren, Shuai Yao
Format Conference Proceeding
LanguageEnglish
Published IEEE 01.10.2014
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:A typical circuit breaker lightning fault of open-ring point in 220kV electromagnetic loop network is analyzed. The lightning intruding into the fracture of circuit breaker causes total internal reflection. And it's the main reason causing the damage of circuit breakers in recent years. Through the analysis, the installation of MOA, in the overhead line entrance of open-ring point in vulnerable area, is the most effective and safe method for prevention of circuit breaker damage events.
DOI:10.1109/ICLP.2014.6973134