Simplified HV tower grounding system model for backflashover simulation
In this paper the authors present and discuss the application of a lumped parameter model, based on a simple π-type network, which is advantageously usable in lightning performance studies of a typical HV European overhead lines (OHLs). This simplified model is able to simulate tower grounding syste...
Saved in:
Published in | 2010 30th International Conference on Lightning Protection (ICLP) pp. 1 - 6 |
---|---|
Main Authors | , , , |
Format | Conference Proceeding |
Language | English |
Published |
University of Cagliari
01.09.2010
|
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | In this paper the authors present and discuss the application of a lumped parameter model, based on a simple π-type network, which is advantageously usable in lightning performance studies of a typical HV European overhead lines (OHLs). This simplified model is able to simulate tower grounding systems also accounting for non-linear ionization phenomena. The behaviour of the simplified grounding system model is compared with the results provided by using a full circuit model, formerly validated by comparison with experimental tests and with simulation results yielded by field models available in literature. Numerical results show a good agreement between the two models; in addition, the proposed π-network model drastically reduces the computational resources (i.e., memory occupation and execution time) required when complex power systems must be studied in transient and non-linear conditions. |
---|---|
DOI: | 10.1109/ICLP.2010.7845914 |