Influence of smoothing reacteor arrangement on transients of converter station for ±500kV double-circuit HVDC system
For HVDC transmission system, the smoothing reactor has two structural types; oil-immersed core reactor and air-core reactor. The former needs to concentrate installed on DC-line, and the latter can be arranged flexibly on both pole line and neutral line. According to the different arrangements of s...
Saved in:
Published in | IEEE PES General Meeting pp. 1 - 8 |
---|---|
Main Authors | , , , , , , , , |
Format | Conference Proceeding |
Language | English |
Published |
IEEE
01.07.2010
|
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | For HVDC transmission system, the smoothing reactor has two structural types; oil-immersed core reactor and air-core reactor. The former needs to concentrate installed on DC-line, and the latter can be arranged flexibly on both pole line and neutral line. According to the different arrangements of smoothing reactors, the system steady-state performance and over-voltage of converter station have some difference. In this paper, the influence of different smoothing reactor arrangements on the system steady-state performance and converter station over-voltage performance of Xiluodu-Guangdong ± 500kV double-circuit HVDC project is analyzed by using ATP/EMTP. A reasonable arrangement of smoothing reactor is proposed, which aims at both maintaining reliability and reducing costs. |
---|---|
ISBN: | 1424465494 9781424465491 |
ISSN: | 1932-5517 |
DOI: | 10.1109/PES.2010.5589913 |