Detection and localization of partial discharge in Air-Insulated Substations using UHF antenna array
UHF-based partial discharge (PD) early warning technique has been tried to monitor and localize PD activities in the whole Air-Insulated Substation (AIS). This paper presents a PD detection and localization system based on this method. This system is composed of four-antenna array (double-cone struc...
Saved in:
Published in | 2016 3rd Conference on Power Engineering and Renewable Energy (ICPERE) pp. 221 - 224 |
---|---|
Main Authors | , , , , , , |
Format | Conference Proceeding |
Language | English |
Published |
IEEE
2016
|
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | UHF-based partial discharge (PD) early warning technique has been tried to monitor and localize PD activities in the whole Air-Insulated Substation (AIS). This paper presents a PD detection and localization system based on this method. This system is composed of four-antenna array (double-cone structure), signal conditioning unit (wide band filter, low-noise amplifier and band-stop filter) and high-speed acquisition unit The main sources of background noise are analyzed and corresponding rejection methods are developed to reduce their effect. The probability-based localization algorithm which comprehensively consider the time differences of multiple signals are proposed to estimate the position of PD source. The developed system is applied to PD detection and location in substations, and the on-site results prove the effectiveness of the system. |
---|---|
DOI: | 10.1109/ICPERE.2016.7904875 |