Measurement and analysis of electromagnetic disturbance at the secondary side of electronic voltage transformer due to switching operations via a 6 kv switchgear
In this paper, the transient disturbance voltage induced at the secondary side of the electronic voltage transformer are measured when the circuit breaker of a 6kV switchgear are open/closed. The typical characteristics of the measured voltage waveform are analyzed. The results show that the wavefor...
Saved in:
Published in | 2017 IEEE 5th International Symposium on Electromagnetic Compatibility (EMC-Beijing) pp. 1 - 4 |
---|---|
Main Authors | , , , |
Format | Conference Proceeding |
Language | English |
Published |
IEEE
01.10.2017
|
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | In this paper, the transient disturbance voltage induced at the secondary side of the electronic voltage transformer are measured when the circuit breaker of a 6kV switchgear are open/closed. The typical characteristics of the measured voltage waveform are analyzed. The results show that the waveform looks like a damped oscillatory wave with peak voltage up to 50.62V, the rise time about 8~16ns, and the dominant frequencies between 1-60MHz. These results are helpful for establishing the immunity test standard waveform for secondary equipment deployed around the switchgear. |
---|---|