The establishment of DC power meter calibration system at China Electric Power Research Institute
The establishment of a DC power meter calibration system using a DC current comparator and a synchronous sampling technique at China Electric Power Research Institute (CEPRI) is described. Measurements can be made at DC voltages ranging from 10mV to 1000V, and DC currents from 10mA to 500A. The syst...
Saved in:
Published in | 29th Conference on Precision Electromagnetic Measurements (CPEM 2014) pp. 408 - 409 |
---|---|
Main Authors | , , , , , , |
Format | Conference Proceeding Journal Article |
Language | English |
Published |
IEEE
01.08.2014
|
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | The establishment of a DC power meter calibration system using a DC current comparator and a synchronous sampling technique at China Electric Power Research Institute (CEPRI) is described. Measurements can be made at DC voltages ranging from 10mV to 1000V, and DC currents from 10mA to 500A. The system features a synchronous voltage/current sampling system and a multi-ratio DC current comparator. The uncertainty of the DC power meter calibration system is estimated to be not more than 120 μW/W. A comparison with another DC power meter calibration system at the National Institute of Metrology China (NIMC) is discussed. |
---|---|
Bibliography: | ObjectType-Article-2 SourceType-Scholarly Journals-1 ObjectType-Conference-1 ObjectType-Feature-3 content type line 23 SourceType-Conference Papers & Proceedings-2 |
ISBN: | 1479952052 9781479952052 |
ISSN: | 0589-1485 2160-0171 |
DOI: | 10.1109/CPEM.2014.6898432 |