On-Line Monitoring Partial Discharge Signal Acquisition Technology of High-Voltage Cable Based on DS-STFT Technology

In view of the research on the high interference and high false alarm rate of partial discharge signals in high-voltage cable online monitoring, a down-sampling short-time Fourier transform (DS-STFT) intelligent partial discharge signal acquisition method is proposed. This method uses DS-STFT to ext...

Full description

Saved in:
Bibliographic Details
Published in2022 4th International Conference on Electrical Engineering and Control Technologies (CEECT) pp. 536 - 539
Main Authors Xiaoxuan, Sun, Hai, Li, Wei, Zhang, Jingjing, Zhou, Jie, Zhou, Chenyuan, Wang
Format Conference Proceeding
LanguageEnglish
Published IEEE 01.12.2022
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:In view of the research on the high interference and high false alarm rate of partial discharge signals in high-voltage cable online monitoring, a down-sampling short-time Fourier transform (DS-STFT) intelligent partial discharge signal acquisition method is proposed. This method uses DS-STFT to extract time-domain spectral features with high recognition and stability, proposes new acquisition trigger conditions on the basis of traditional threshold- time acquisition, and applies it to high-voltage cable partial line monitoring scenarios. The experimental results show that the trigger accuracy of this method is more than 96%, and it has been applied to the partial discharge on-line monitoring of a 110kV high-voltage cable line. It has been proved that this method can effectively detect the suspected PD pulse signal.
DOI:10.1109/CEECT55960.2022.10030594