Implementation of Instantaneous Symmetrical Component Theory based Hysteresis Controller for DSTATCOM
This article come up with the compensation of power quality problems in a distribution system by providing Instantaneous Symmetrical Component Theory (ISCT) based hysteresis control scheme for Distribution Static Compensator (DSTATCOM) in Voltage Control Mode (VCM). The proposed scheme generates ref...
Saved in:
Published in | 2021 International Conference on Advancements in Electrical, Electronics, Communication, Computing and Automation (ICAECA) pp. 1 - 8 |
---|---|
Main Authors | , , , , , |
Format | Conference Proceeding |
Language | English |
Published |
IEEE
08.10.2021
|
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | This article come up with the compensation of power quality problems in a distribution system by providing Instantaneous Symmetrical Component Theory (ISCT) based hysteresis control scheme for Distribution Static Compensator (DSTATCOM) in Voltage Control Mode (VCM). The proposed scheme generates reference currents by considering instantaneous values of zero, positive and negative sequence components of load currents. The capability of the proposed controller is verified underbalanced and unbalanced, linear and nonlinear conditions in PSCAD/EMTDC platform and the performance is found satisfactory. |
---|---|
DOI: | 10.1109/ICAECA52838.2021.9675526 |