On-site measurement of tracer gas transmission between horizontal adjacent flats in residential building and cross-infection risk assessment

Airborne transmission is a main spread mode of respiratory infectious diseases, whose frequent epidemic has brought serious social burden. Identifying possible routes of the airborne transmission and predicting the potential infection risk are meaningful for infectious disease control. In the presen...

Full description

Saved in:
Bibliographic Details
Published inBuilding and environment Vol. 99; pp. 13 - 21
Main Authors Wu, Yan, Tung, Thomas C.W., Niu, Jian-lei
Format Journal Article
LanguageEnglish
Published England Elsevier Ltd 01.04.2016
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:Airborne transmission is a main spread mode of respiratory infectious diseases, whose frequent epidemic has brought serious social burden. Identifying possible routes of the airborne transmission and predicting the potential infection risk are meaningful for infectious disease control. In the present study, an internal spread route between horizontal adjacent flats induced by air infiltration was investigated. On-site measurements were conducted, and tracer gas technique was employed. Two measurement scenarios, closed window mode and open window mode, were compared. Using the calculated air change rate and mass fraction, the cross-infection risk was estimated using the Wells–Riley model. It found that tracer gas concentrations in receptor rooms are one order lower than the source room, and the infection risks are also one order lower. Opening windows results in larger air change rate on the one hand, but higher mass fraction on the other hand. Higher mass fraction not necessarily results in higher infection risk as the pathogen concentration in the source room is reduced by the higher air change rate. In the present study, opening windows could significantly reduce the infection risk of the index room but slightly reduce the risks in receptor rooms. The mass fraction of air originated from the index room to the receptor units could be 0.28 and the relative cross-infection risk through the internal transmission route could be 9%, which are higher than the external spread through single-sided window flush. The study implicates that the horizontal transmission route induced by air infiltration should not be underestimated. •On-site measurements were carried out to explore possible airborne transmission route.•A spread route between horizontal adjacent units induced by air infiltration was verified.•The relative cross-infection risk was assessed using the Wells–Riley model.•The risk of the verified route may be higher than that due to single-side open window plume.
Bibliography:ObjectType-Article-1
SourceType-Scholarly Journals-1
ObjectType-Feature-2
content type line 23
ISSN:0360-1323
1873-684X
DOI:10.1016/j.buildenv.2016.01.013