Experimental study on titanium heat exchanger used in a gas fired water heater for latent heat recovery

In general, latent heat recovery is usually accompanied by the corrosion of the heat exchanger, which is caused by the strongly acidic condensate when the temperature of the flue gas is lowered below the acid dew point. The present study has been conducted to investigate the heat and mass transfer c...

Full description

Saved in:
Bibliographic Details
Published inApplied thermal engineering Vol. 30; no. 17; pp. 2730 - 2737
Main Authors Hwang, Kyudae, Song, Chan ho, Saito, Kiyoshi, Kawai, Sunao
Format Journal Article
LanguageEnglish
Published Kidlington Elsevier Ltd 01.12.2010
Elsevier
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:In general, latent heat recovery is usually accompanied by the corrosion of the heat exchanger, which is caused by the strongly acidic condensate when the temperature of the flue gas is lowered below the acid dew point. The present study has been conducted to investigate the heat and mass transfer characteristics in a titanium heat exchanger with excellent corrosion resistance used for waste heat recovery with the condensation arranged in a gas fired water heater. In addition, the thermal efficiency of the gas fired water heater was evaluated based on the net calorific value at the maximum rated output during latent heat recovery from the exhaust flue gas. Parametric studies were conducted for the flue gas flow rate, inlet temperature and mass flow rate of the supplied water, respectively. Different arrangements of the tubes of the heat exchanger including in-line and staggered configurations were investigated. The experimental results indicate that the thermal efficiency of the gas fired water heater with a latent heat recovery (LHR) heat exchanger was enhanced by about 10% compared with conventional instantaneous water heaters, i.e., water heaters without heat recovery. In addition, in terms of the Nusselt number and the Sherwood number, the heat and mass transfer performance of the staggered tube bank type were approximately 50% and 10% higher than that on the in-line tube bank type when the Reynolds number of the flue gas was 10 3. ► The characteristics of heat mass transfer in an LHR with crushed titanium tubes. ► Thermal efficiency increases up to 93% by LHR using titanium heat exchanger. ► The UA of the staggered tube bank type is about 2 times higher than in-line tube bank. ► Heat and mass transfer performance of the staggered tube bank is 50%, 10% higher.
Bibliography:ObjectType-Article-1
SourceType-Scholarly Journals-1
ObjectType-Feature-2
content type line 23
ISSN:1359-4311
DOI:10.1016/j.applthermaleng.2010.07.027