Experimental investigation of a data-centre cooling system using a new single-phase immersion/liquid technique

This paper presents an experimental investigation conducted on a new single-phase immersion/liquid-cooling technique developed at the OVHcloud laboratory, combining a direct-to-chip water-cooling system with passive single-immersion cooling technology. The experimental setup tested the impact of thr...

Full description

Saved in:
Bibliographic Details
Published inCase studies in thermal engineering Vol. 45; p. 102925
Main Authors Hnayno, Mohamad, Chehade, Ali, Klaba, Henryk, Polidori, Guillaume, Maalouf, Chadi
Format Journal Article
LanguageEnglish
Published Elsevier Ltd 01.05.2023
Elsevier
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:This paper presents an experimental investigation conducted on a new single-phase immersion/liquid-cooling technique developed at the OVHcloud laboratory, combining a direct-to-chip water-cooling system with passive single-immersion cooling technology. The experimental setup tested the impact of three dielectric fluids (S5X, SmartCoolant and ThermaSafe R), the effect of the water circuit configuration, and the server power/profile. Results suggest that the system cooling demand depends on the fluid's viscosity. As the viscosity increased from 4.6 to 9.8 mPa s, the cooling performance decreased by approximately 6%. Moreover, all the IT server profiles were validated at various water inlet temperatures and flow rates. The energy performance of the proposed technique and the liquid-cooling system previously used by OVHcloud was compared at a 600 kW data centre (DC). The proposed technique showed a reduction in the DC electrical power consumption by at least 20.7% compared to the liquid-cooling system. Finally, the cooling performance of the air- and liquid-cooled systems and the proposed solution was compared computationally at the server level. When using the proposed solution, the energy consumed per server was reduced by at least 20% compared with the air-cooling system and 7% compared with liquid-cooling system. [Display omitted]
ISSN:2214-157X
2214-157X
DOI:10.1016/j.csite.2023.102925