The fluorinated olefin R-1234ze(Z) as a high-temperature heat pumping refrigerant

Estimates are provided for R-1234ze(Z) of its: (1) critical temperature, pressure, and density, acentric factor, and ideal gas specific heat at constant pressure, and (2) various thermodynamic and transport properties, which are used to predict the performance potential of R-1234ze(Z) in high-temper...

Full description

Saved in:
Bibliographic Details
Published inInternational journal of refrigeration Vol. 32; no. 6; pp. 1412 - 1422
Main Authors Brown, J. Steven, Zilio, Claudio, Cavallini, Alberto
Format Journal Article
LanguageEnglish
Published Kidlington Elsevier Ltd 01.09.2009
Elsevier
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:Estimates are provided for R-1234ze(Z) of its: (1) critical temperature, pressure, and density, acentric factor, and ideal gas specific heat at constant pressure, and (2) various thermodynamic and transport properties, which are used to predict the performance potential of R-1234ze(Z) in high-temperature heat pumping applications. In particular, for an idealized cycle, the coefficient of performance and volumetric heating capacity for R-114 are 3.24 and 1667 kW m −3, respectively, and for R-1234ze(Z) are 3.40 and 1645 kW m −3, respectively. The attractiveness of R-1234ze(Z) is confirmed further through heat exchanger simulations. This paper demonstrates that R-1234ze(Z) deserves further consideration as a possible R-114 replacement.
ISSN:0140-7007
1879-2081
DOI:10.1016/j.ijrefrig.2009.03.002