Air side heat transfer coefficients of discrete plate finned-tube heat exchangers with large fin pitch
The objective of this study is to investigate the heat transfer characteristics of discrete plate finned-tube heat exchangers with large fin pitches. Thirty-four heat exchangers were tested with variations of fin pitches, the number of tube rows, fin alignment, and vertical fin space. The j-factor o...
Saved in:
Published in | Applied thermal engineering Vol. 30; no. 2; pp. 174 - 180 |
---|---|
Main Authors | , , , |
Format | Journal Article |
Language | English |
Published |
Kidlington
Elsevier Ltd
01.02.2010
Elsevier |
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | The objective of this study is to investigate the heat transfer characteristics of discrete plate finned-tube heat exchangers with large fin pitches. Thirty-four heat exchangers were tested with variations of fin pitches, the number of tube rows, fin alignment, and vertical fin space. The
j-factor of the discrete plate finned-tube exchanger was analyzed as a function of coil geometry and then compared with that of the continuous plate finned-tube heat exchanger. For fin pitches of 7.5–15
mm, the
j-factors of the discrete plate finned-tube heat exchangers were 6.0–11.6% higher than those of the continuous plate finned-tube heat exchangers. Two separate correlations for the
j-factor were developed for the inline and the staggered fin alignment in the discrete plate finned-tube heat exchangers to predict the measured data within a relative deviation of 2.9%. |
---|---|
Bibliography: | ObjectType-Article-2 SourceType-Scholarly Journals-1 ObjectType-Feature-1 content type line 23 |
ISSN: | 1359-4311 |
DOI: | 10.1016/j.applthermaleng.2009.08.001 |