A novel SVM-based decision framework considering feature distribution for Power Transformer Fault Diagnosis

International Electrotechnical Commission (IEC) proposed the IEC three-ratio method based on Dissolved Gas Analysis (DGA), which is one of the most effective tools for Power Transformer Fault Diagnosis (PTFD). However, the PTFD accuracy is generally limited because the classification boundary could...

Full description

Saved in:
Bibliographic Details
Published inEnergy reports Vol. 8; pp. 9392 - 9401
Main Authors Hong, Lucheng, Chen, Zehua, Wang, Yifei, Shahidehpour, Mohammad, Wu, Minghe
Format Journal Article
LanguageEnglish
Published Elsevier Ltd 01.11.2022
Elsevier
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:International Electrotechnical Commission (IEC) proposed the IEC three-ratio method based on Dissolved Gas Analysis (DGA), which is one of the most effective tools for Power Transformer Fault Diagnosis (PTFD). However, the PTFD accuracy is generally limited because the classification boundary could be too stiff to classify samples located near the boundary. The Support Vector Machine (SVM) was applied to PTFD to improve diagnosis accuracy, while traditional SVM multi-classification methods and parameter optimization algorithms are subject to poor training efficiency. As a result, the SVM-based PTFD model is difficult to update frequently with the accumulation of fault data. A new SVM-based PTFD decision framework is proposed in this paper which can significantly boost the training efficiency and ensure the accuracy. In the proposed framework, a multi-step feature extraction process consisting of characteristic gas concentration and its ratios is applied. Based on the feature distribution of various samples, a proper SVM multi-classification method is presented using a hierarchical decision tree structure. In addition, according to the principles of SVM and radial basis kernel function, a Support Vector feature-based parameter optimization algorithm (SVFB) is proposed. IEC TC 10 data and the historical data of online transformer monitoring provided by the State Grid Corporation of China are adopted as sample sets. The simulation results demonstrate that the proposed decision framework can reach high diagnosis accuracy while shortening the training time.
ISSN:2352-4847
2352-4847