Electric field characteristics of X-ray detection and safety protection in live work of transmission lines

Hidden defects in transmission lines can be detected by X-ray. Through the simulation of different voltage/current tests in the laboratory, the live detection test of digital X-ray detection equipment was carried out and the detection tests under the live condition of 110kV transmission line carried...

Full description

Saved in:
Bibliographic Details
Published inIOP conference series. Earth and environmental science Vol. 546; no. 2; pp. 22052 - 22060
Main Authors Xianhui, Cao, Kejian, Ouyang, Weike, Liu, Yi, Xie, Miao, Yang, Chao, Feng, Yi, Fu, Long, Zhan
Format Journal Article
LanguageEnglish
Published Bristol IOP Publishing 01.07.2020
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:Hidden defects in transmission lines can be detected by X-ray. Through the simulation of different voltage/current tests in the laboratory, the live detection test of digital X-ray detection equipment was carried out and the detection tests under the live condition of 110kV transmission line carried by unmanned aerial vehicle, the maximum tolerable voltage of X-ray digital imaging equipment during live operation was determined. By using the electric field finite element simulation, the affected field intensity detected by the equipment is 360kV/m, and the spatial field intensity distribution of ac transmission lines with different voltage levels is given, which provides a reference for selecting reasonable electric field shielding measures for the live operation of X-ray digital imaging equipment.
ISSN:1755-1307
1755-1315
DOI:10.1088/1755-1315/546/2/022052