Electric field characteristics of X-ray detection and safety protection in live work of transmission lines
Hidden defects in transmission lines can be detected by X-ray. Through the simulation of different voltage/current tests in the laboratory, the live detection test of digital X-ray detection equipment was carried out and the detection tests under the live condition of 110kV transmission line carried...
Saved in:
Published in | IOP conference series. Earth and environmental science Vol. 546; no. 2; pp. 22052 - 22060 |
---|---|
Main Authors | , , , , , , , |
Format | Journal Article |
Language | English |
Published |
Bristol
IOP Publishing
01.07.2020
|
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | Hidden defects in transmission lines can be detected by X-ray. Through the simulation of different voltage/current tests in the laboratory, the live detection test of digital X-ray detection equipment was carried out and the detection tests under the live condition of 110kV transmission line carried by unmanned aerial vehicle, the maximum tolerable voltage of X-ray digital imaging equipment during live operation was determined. By using the electric field finite element simulation, the affected field intensity detected by the equipment is 360kV/m, and the spatial field intensity distribution of ac transmission lines with different voltage levels is given, which provides a reference for selecting reasonable electric field shielding measures for the live operation of X-ray digital imaging equipment. |
---|---|
ISSN: | 1755-1307 1755-1315 |
DOI: | 10.1088/1755-1315/546/2/022052 |