Evaluation of corrosion inhibitors for cooling water systems operating at high concentration cycles
The present work aimed at evaluating AISI 1020 carbon steel corrosion resistance of a 6:4:1:1 (MoO 42−/HEDP/PO 43−/Zn2+) inhibitor mixture present in a solution which simulates an industrial cooling water system operating at high concentration cycles (1050 ppm Cl− and 450 ppm Ca2+). High concentrati...
Saved in:
Published in | Materials and corrosion Vol. 60; no. 5; pp. 323 - 329 |
---|---|
Main Authors | , , , |
Format | Journal Article |
Language | English |
Published |
Weinheim
WILEY-VCH Verlag
01.05.2009
WILEY‐VCH Verlag Wiley-VCH |
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | The present work aimed at evaluating AISI 1020 carbon steel corrosion resistance of a 6:4:1:1 (MoO 42−/HEDP/PO 43−/Zn2+) inhibitor mixture present in a solution which simulates an industrial cooling water system operating at high concentration cycles (1050 ppm Cl− and 450 ppm Ca2+). High concentration cycles are desirable, because system purge and treated water consumption are decreased. On the other hand, a high number of concentration cycles can increase the concentration of salts and dissolved impurities, causing corrosion, incrustations, and deposits inside the pipes, heat exchangers, and cooling towers. Thus, the chloride (Cl−) and calcium (Ca2+) ions aggressiveness was studied on the proposed inhibiting mixture, at the temperatures of 40 and 60 °C, through electrochemical techniques like open circuit potential measurements, anodic and cathodic polarization, and weight loss. The results showed that the inhibitor mixture conferred adequate protection to carbon steel in low concentrations, even in high aggressive media. |
---|---|
Bibliography: | ArticleID:MACO200805098 ark:/67375/WNG-LQ6KCL5D-B istex:045039043D6155E706F7BAB72F778B4612A6DB03 ObjectType-Article-2 SourceType-Scholarly Journals-1 ObjectType-Feature-1 content type line 23 |