Long-term on-site assessment of hygrothermal performance of interior thermal insulation system without water vapour barrier

On-site assessment of hygric and thermal performance of an interior thermal insulation system on the basis of hydrophilic mineral wool is presented in the paper. The system is applied during the summer period on a brick-built house from the end of 19th century. Hygrothermal testing is done during th...

Full description

Saved in:
Bibliographic Details
Published inEnergy and buildings Vol. 41; no. 1; pp. 51 - 55
Main Authors Toman, Jan, Vimmrová, Alena, Černý, Robert
Format Journal Article
LanguageEnglish
Published Oxford Elsevier B.V 2009
Elsevier
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:On-site assessment of hygric and thermal performance of an interior thermal insulation system on the basis of hydrophilic mineral wool is presented in the paper. The system is applied during the summer period on a brick-built house from the end of 19th century. Hygrothermal testing is done during the time period of 4 years. The reconstructed building envelope exhibits very good hygrothermal performance. The thermal resistance increases approximately two times. Water condensation is never observed inside the envelope during the whole testing period. A comparison with the previous experiment in semi-scale conditions which was performed for similar insulation system constructed during the winter season shows that the precedence should be given to the application of the system in summer period as it is more considerate to the old masonry.
Bibliography:ObjectType-Article-2
SourceType-Scholarly Journals-1
ObjectType-Feature-1
content type line 23
ISSN:0378-7788
DOI:10.1016/j.enbuild.2008.07.007