The Characteristic Temperature in the Definition of Heat Transfer Coefficient on the Fin Side Surface in Tube Bank Fin Heat Exchanger
The characteristic temperature in the definition of the fin side surface heat transfer coefficient of two tube bank fin heat exchangers is investigated in detail. The results reveal that if the average temperature of the fin side fluid is used in the definition of the fin side surface coefficient, a...
Saved in:
Published in | Numerical heat transfer. Part A, Applications Vol. 60; no. 10; pp. 848 - 866 |
---|---|
Main Authors | , , , , , |
Format | Journal Article |
Language | English |
Published |
Philadelphia
Taylor & Francis Group
15.11.2011
Taylor & Francis Ltd |
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | The characteristic temperature in the definition of the fin side surface heat transfer coefficient of two tube bank fin heat exchangers is investigated in detail. The results reveal that if the average temperature of the fin side fluid is used in the definition of the fin side surface coefficient, a small discrepancy between the numerical and experimental results is obtained. The results not only give a technical definition of the characteristic temperature of the fin side surface heat transfer coefficient, but also imply that the discrepancy between experimental and numerical results may come from incorrect use of the characteristic temperature. |
---|---|
Bibliography: | ObjectType-Article-1 SourceType-Scholarly Journals-1 ObjectType-Feature-2 content type line 23 |
ISSN: | 1040-7782 1521-0634 |
DOI: | 10.1080/10407782.2011.616850 |