Evaluation of temperature rise of distribution transformers in the presence of harmonics and distortion

Core and copper losses of a distribution transformer increase in the presence of harmonics and distortion. In most of the cases, an indication of total harmonic distortion is known. Expressions for the transformer core and winding losses as a function of the total harmonic distortion are obtained ex...

Full description

Saved in:
Bibliographic Details
Published inElectric power systems research Vol. 20; no. 1; pp. 15 - 22
Main Authors Girgis, Adly A., Makram, Elham B., Nims, Joseph W., O'Dell, Larry K.
Format Journal Article
LanguageEnglish
Published Amsterdam Elsevier B.V 01.12.1990
Elsevier
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:Core and copper losses of a distribution transformer increase in the presence of harmonics and distortion. In most of the cases, an indication of total harmonic distortion is known. Expressions for the transformer core and winding losses as a function of the total harmonic distortion are obtained experimentally using a harmonic generator, a 10 kVA 7200/120 V distribution transformer, and a digital oscilloscope equipped with digital processing software. The selection of the harmonics is based on actual recorded data. A thermal model of a distribution transformer is used to evaluate the temperature rise both with and without harmonics. The evaluation indicates that there is a significant increase in the operating temperature in the presence of high order harmonics, as compared with the operating temperatures when no harmonics are present. This paper presents the nature of the actual recorded data, the method of evaluation, and the results.
Bibliography:ObjectType-Article-2
SourceType-Scholarly Journals-1
ObjectType-Feature-1
content type line 23
ISSN:0378-7796
1873-2046