Icing Condition Assessment of In-Service Glass Insulators Based on Graphical Shed Spacing and Graphical Shed Overhang

Icing on transmission lines might lead to ice flashovers of insulators, collapse of towers, tripping faults of transmission lines, and other accidents. Shed spacing and shed overhang of insulators are clues for evaluating the probability of ice flashover. This paper researches image-processing metho...

Full description

Saved in:
Bibliographic Details
Published inEnergies (Basel) Vol. 11; no. 2; p. 318
Main Authors Hao, Yanpeng, Wei, Jie, Jiang, Xiaolan, Yang, Lin, Li, Licheng, Wang, Junke, Li, Hao, Li, Ruihai
Format Journal Article
LanguageEnglish
Published Basel MDPI AG 01.02.2018
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:Icing on transmission lines might lead to ice flashovers of insulators, collapse of towers, tripping faults of transmission lines, and other accidents. Shed spacing and shed overhang of insulators are clues for evaluating the probability of ice flashover. This paper researches image-processing methods for the natural icing of in-service glass insulators. Calculation methods of graphical shed spacing and graphical shed overhang are proposed via recognizing the convexity defects of the contours of an icing insulator string based on the GrabCut segmentation algorithm. The experiments are carried out with image data from our climatic chamber and the China Southern Power Grid Disaster (Icing) Warning System of Transmission Lines. The results show that the graphical shed overhang of insulators show evident change due to icing. This method can recognize the most serious icing conditions where the insulator sheds are completely bridged. Also, it can detect bridging positions including the left side, right side, or both sides of the insulator strings in the images.
ISSN:1996-1073
1996-1073
DOI:10.3390/en11020318