Simulation of an adsorption solar cooling system
A more realistic theoretical simulation model for a tubular solar adsorption refrigerating system using activated carbon–methanol (AC/M) pair has been introduced. The mathematical model represents the heat and mass transfer inside the adsorption bed, the condenser, and the evaporator. The simulation...
Saved in:
Published in | Energy (Oxford) Vol. 36; no. 1; pp. 530 - 537 |
---|---|
Main Authors | , , |
Format | Journal Article |
Language | English |
Published |
Kidlington
Elsevier Ltd
2011
Elsevier |
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | A more realistic theoretical simulation model for a tubular solar adsorption refrigerating system using activated carbon–methanol (AC/M) pair has been introduced. The mathematical model represents the heat and mass transfer inside the adsorption bed, the condenser, and the evaporator. The simulation technique takes into account the variations of ambient temperature and solar radiation along the day. Furthermore, the local pressure, and local thermal conductivity variations in space and time inside the tubular reactor are investigated as well. A C++ computer program is written to solve the proposed numerical model using the finite difference method. The developed program covers the operations of all the system components along the cycle time. The performance of the tubular reactor, the condenser, and the evaporator has been discussed. Time allocation chart and switching operations for the solar refrigeration system processes are illustrated as well. The case studied has a 1 m
2 surface area solar flat plate collector integrated with a 20 stainless steel tubes containing the AC/M pair and each tube has a 5 cm outer diameter. In addition, the condenser pressure is set to 54.2 kpa. It has been found that, the solar coefficient of performance and the specific cooling power of the system are 0.211 and 2.326 respectively. In addition, the pressure distribution inside the adsorption bed has been found nearly uniform and varying only with time. Furthermore, the AC/M thermal conductivity is shown to be constant in both space and time. |
---|---|
Bibliography: | http://dx.doi.org/10.1016/j.energy.2010.10.011 |
ISSN: | 0360-5442 |
DOI: | 10.1016/j.energy.2010.10.011 |