Effect of load characteristics on maximum power transfer limit for HV compensated transmission lines
In this paper a new method for calculating the maximum power transfer limit of high voltage compensated transmission lines is made. The effect of load characteristics as function of voltage and frequency is taken into account. Two schemes using series and shunt compensation are studied and numerical...
Saved in:
Published in | International journal of electrical power & energy systems Vol. 26; no. 7; pp. 467 - 472 |
---|---|
Main Authors | , , |
Format | Journal Article |
Language | English |
Published |
Oxford
Elsevier Ltd
01.09.2004
Elsevier |
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | In this paper a new method for calculating the maximum power transfer limit of high voltage compensated transmission lines is made. The effect of load characteristics as function of voltage and frequency is taken into account. Two schemes using series and shunt compensation are studied and numerical results for maximum power transfer limit, critical angular separation and critical voltage are given. These schemes are applied to the existing AC 500 kV transmission line connected between High-Dam and Cairo in Egypt. |
---|---|
ISSN: | 0142-0615 1879-3517 |
DOI: | 10.1016/j.ijepes.2003.12.008 |