Transient-state analysis of MV instrument transformers
•Analysis of MV instrument transformers in transient-state.•Overvoltages transferred from primary windings to the secondary ones when a fast voltage impulse excites machines.•Comparison of the results obtained through experimental tests and a theoretical study. This study illustrates how selected in...
Saved in:
Published in | Electric power systems research Vol. 168; pp. 162 - 168 |
---|---|
Main Authors | , , , , , |
Format | Journal Article |
Language | English |
Published |
Amsterdam
Elsevier B.V
01.03.2019
Elsevier Science Ltd |
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | •Analysis of MV instrument transformers in transient-state.•Overvoltages transferred from primary windings to the secondary ones when a fast voltage impulse excites machines.•Comparison of the results obtained through experimental tests and a theoretical study.
This study illustrates how selected instrument voltage transformers (VTs-I) behave in a transitory state. Some laboratory tests are conducted on medium voltage (MV) inductive voltage types to evaluate the voltage transferred from primary to secondary windings when a fast voltage impulse (1.2/50μs) excites three machines constructively in different ways. Possible effects of metal parts present in the laboratory on the VTs-I behavior are analyzed, and other tests are conducted to determine a suitable shielding for the VTs-I. In order to interpret the experimental results, a theoretical study is performed using a simplified model of the instrument transformer. Finally, characteristic parameters are assigned values that were derived from experimental tests. |
---|---|
ISSN: | 0378-7796 1873-2046 |
DOI: | 10.1016/j.epsr.2018.11.015 |