The Seismic Safety Assessment of 170 kV GIS (Gas-Insulated Switchgear) by the Seismic Test on the Large Shaking Table and by the Finite Element Analysis with Korean and IEC Seismic Standards
This paper describes the seismic test and numerical stress analysis of a 170 kV Gas-insulated switchgear (GIS) to see the structural and operational safety. Both the seismic test and numerical FEA (finite element analysis) are performed according to the procedure of Korean and International (IEC-622...
Saved in:
Published in | Journal of electrical engineering & technology Vol. 15; no. 6; pp. 2675 - 2684 |
---|---|
Main Authors | , , , , , |
Format | Journal Article |
Language | English |
Published |
Singapore
Springer Singapore
01.11.2020
대한전기학회 |
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | This paper describes the seismic test and numerical stress analysis of a 170 kV Gas-insulated switchgear (GIS) to see the structural and operational safety. Both the seismic test and numerical FEA (finite element analysis) are performed according to the procedure of Korean and International (IEC-62271) seismic standards. The GIS is mounted on the shaking table for a seismic test at KIMM (Korea Institute of Machinery and Material) to see the stress level and safety under earthquake loading conditions. The FEA analysis is performed to compare with the seismic test. Both the natural frequency (NF) and stress results from the numerical computation and seismic test are close and show adequate electrical and structural safety margin. |
---|---|
ISSN: | 1975-0102 2093-7423 |
DOI: | 10.1007/s42835-020-00503-9 |