Model Predictive Decoupled Active and Reactive Power Control for High-Power Grid-Connected Four-Level Diode-Clamped Inverters
In this paper, a model predictive scheme is proposed to control the grid-connected high-power four-level diode-clamped inverter. To predict the future behavior of active and reactive grid power values and dc link capacitor voltages, a discrete-time model of the inverter is developed in synchronous r...
Saved in:
Published in | IEEE transactions on industrial electronics (1982) Vol. 61; no. 7; pp. 3407 - 3416 |
---|---|
Main Authors | , |
Format | Journal Article |
Language | English |
Published |
New York
IEEE
01.07.2014
The Institute of Electrical and Electronics Engineers, Inc. (IEEE) |
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | In this paper, a model predictive scheme is proposed to control the grid-connected high-power four-level diode-clamped inverter. To predict the future behavior of active and reactive grid power values and dc link capacitor voltages, a discrete-time model of the inverter is developed in synchronous reference frame. The controller uses all the possible switching states of the inverter for the prediction and evaluates them using a cost function. The switching state, which minimizes the cost function, is then chosen and applied at the next sampling interval. The switching frequency minimization is also achieved by including an extra constraint in the cost function. A simplified extrapolation method with reduced computational burden is proposed to safeguard the semiconductor devices during the dynamic changes in reference power values. The performance of the proposed method is investigated with the perturbations in the grid filter and dc link parameters. The feasibility of the proposed method is verified through simulation and experimental results, showing good dynamic and steady-state performance. |
---|---|
Bibliography: | ObjectType-Article-1 SourceType-Scholarly Journals-1 ObjectType-Feature-2 content type line 14 content type line 23 |
ISSN: | 0278-0046 1557-9948 |