Differential relay reliability enhancement using fourth harmonic for a large power transformer
A differential relay that is very sensitive relay operating even at its limits may be used for protecting a power transformer. However, this characteristic may lead to unnecessary tripping due to transient currents such as an inrush and over excitation current. In order to avoid this mal-operation o...
Saved in:
Published in | International journal of system assurance engineering and management Vol. 8; no. Suppl 2; pp. 592 - 598 |
---|---|
Main Authors | , |
Format | Journal Article |
Language | English |
Published |
New Delhi
Springer India
01.11.2017
Springer Nature B.V |
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | A differential relay that is very sensitive relay operating even at its limits may be used for protecting a power transformer. However, this characteristic may lead to unnecessary tripping due to transient currents such as an inrush and over excitation current. In order to avoid this mal-operation of the relay, a second and fifth harmonic blocking technique has been used; however this technique is not reliable if a second harmonic magnitude is weak. In this paper, a new approach is proposed using even harmonics (second and fourth). The test results show that this proposed approach is a good blocking technique associated with the differential relay even for large modern power transformer which has small second harmonic as well; it provides a good discrimination between the transient currents and the internal fault currents during internal fault. |
---|---|
ISSN: | 0975-6809 0976-4348 |
DOI: | 10.1007/s13198-016-0475-6 |