Differential relay reliability enhancement using fourth harmonic for a large power transformer

A differential relay that is very sensitive relay operating even at its limits may be used for protecting a power transformer. However, this characteristic may lead to unnecessary tripping due to transient currents such as an inrush and over excitation current. In order to avoid this mal-operation o...

Full description

Saved in:
Bibliographic Details
Published inInternational journal of system assurance engineering and management Vol. 8; no. Suppl 2; pp. 592 - 598
Main Authors Bouderbala, Rachid, Bentarzi, Hamid
Format Journal Article
LanguageEnglish
Published New Delhi Springer India 01.11.2017
Springer Nature B.V
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:A differential relay that is very sensitive relay operating even at its limits may be used for protecting a power transformer. However, this characteristic may lead to unnecessary tripping due to transient currents such as an inrush and over excitation current. In order to avoid this mal-operation of the relay, a second and fifth harmonic blocking technique has been used; however this technique is not reliable if a second harmonic magnitude is weak. In this paper, a new approach is proposed using even harmonics (second and fourth). The test results show that this proposed approach is a good blocking technique associated with the differential relay even for large modern power transformer which has small second harmonic as well; it provides a good discrimination between the transient currents and the internal fault currents during internal fault.
ISSN:0975-6809
0976-4348
DOI:10.1007/s13198-016-0475-6