Effect of reduced evaporator airflow on the high temperature performance of air conditioners
Two residential sized air conditioners were tested in psychrometric rooms at reduced evaporator airflows ranging from 0 to 50% below that recommended by the manufacture of each of the units. Outdoor temperatures ranged from 35 to 49°C. One of the units used a thermal expansion valve for flow control...
Saved in:
Published in | Energy and buildings Vol. 24; no. 3; pp. 195 - 201 |
---|---|
Main Authors | , , , |
Format | Journal Article |
Language | English |
Published |
Elsevier B.V
01.10.1996
|
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | Two residential sized air conditioners were tested in psychrometric rooms at reduced evaporator airflows ranging from 0 to 50% below that recommended by the manufacture of each of the units. Outdoor temperatures ranged from 35 to 49°C. One of the units used a thermal expansion valve for flow control while the other unit used a short tube orifice. Performance of the units was quantified by the capacity, power, coefficient of performance, and sensible heat ratio. Results at 35°C indicated that the reduction in air produced a larger drop in capacity and coefficient of performance for the orifice controlled unit than the thermal expansion valve controlled unit. The power showed less than a 4% reduction for either unit as the airflow was reduced by 50%. |
---|---|