BCR intercomparison of AC-DC current transfer standards

The established national standards for ac-dc current transfer and the respective measurement set-ups of Denmark, France, Germany, Italy, Sweden, and The Netherlands were intercompared in the current range from 10 mA to 20 A and in the frequency range from 10 Hz to 100 kHz. An agreement within 10 ppm...

Full description

Saved in:
Bibliographic Details
Published inIEEE transactions on instrumentation and measurement Vol. 44; no. 2; pp. 403 - 406
Main Authors Klonz, M., Bergeest, R., Caizergues, A., Fraisse, D., Winther, C.A.D., Pogliano, U., Cabiati, F., Bosco, G.C., Zago, G., Dessens, J.T., de Vreede, J.P.M., Rydler, K.-E., Nilsson, H.
Format Journal Article Conference Proceeding
LanguageEnglish
Published New York, NY IEEE 01.04.1995
Institute of Electrical and Electronics Engineers
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:The established national standards for ac-dc current transfer and the respective measurement set-ups of Denmark, France, Germany, Italy, Sweden, and The Netherlands were intercompared in the current range from 10 mA to 20 A and in the frequency range from 10 Hz to 100 kHz. An agreement within 10 ppm to 30 ppm was obtained up to 100 mA, degrading to 100 ppm at 1 A (100 kHz) and 70 ppm at 10 A (20 kHz) and 20 A (5 kHz).< >
Bibliography:ObjectType-Article-2
SourceType-Scholarly Journals-1
ObjectType-Feature-1
content type line 23
ISSN:0018-9456
1557-9662