Exploring Remote Monitoring of Degraded Compression and Bolted Joints in HV Power Transmission Lines

In this work preliminary yet comprehensive considerations are reported on the possibility for remote monitoring of degraded compression and bolted joints on high voltage overhead power lines. Measurements are performed on new, naturally aged, and artificially degraded joints to quantify the impedanc...

Full description

Saved in:
Bibliographic Details
Published inIEEE transactions on power delivery Vol. 31; no. 5; pp. 2179 - 2187
Main Authors de Paulis, F., Olivieri, C., Orlandi, A., Giannuzzi, G., Bassi, F., Morandini, C., Fiorucci, E., Bucci, G.
Format Journal Article
LanguageEnglish
Published New York IEEE 01.10.2016
The Institute of Electrical and Electronics Engineers, Inc. (IEEE)
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:In this work preliminary yet comprehensive considerations are reported on the possibility for remote monitoring of degraded compression and bolted joints on high voltage overhead power lines. Measurements are performed on new, naturally aged, and artificially degraded joints to quantify the impedance discontinuity introduced along typical HV overhead lines. Numerical simulations, a preliminary time domain reflectometry (TDR) measurement campaign, and circuit simulations are performed on a real power line to study the TDR-based capabilities for the identification of the investigated joint impedances. This study sets the basic concepts to the development of a remote monitoring system for quantifying and locating degraded joints.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2016.2562579