VDCOL Parameter Optimization Method for Improving Voltage Stability of DC Receiving Terminal Power Grid
Abstract This research based on different startup and operation modes of Heilongjiang receiving power grid, The influence of anti disturbance capability of converter bus on DC recovery characteristics. A VDCOL parameter optimization configuration scheme based on multi feed short circuit ratio (MSCR)...
Saved in:
Published in | Journal of physics. Conference series Vol. 2503; no. 1; pp. 12077 - 12080 |
---|---|
Main Authors | , , , , , |
Format | Journal Article |
Language | English |
Published |
Bristol
IOP Publishing
01.05.2023
|
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | Abstract
This research based on different startup and operation modes of Heilongjiang receiving power grid, The influence of anti disturbance capability of converter bus on DC recovery characteristics. A VDCOL parameter optimization configuration scheme based on multi feed short circuit ratio (MSCR) is proposed. Through the DC near fault simulation analysis, it is verified that the proposed VDCOL parameter optimization scheme reduces the overall wattless power demand of converter station, and improve Heilongjiang receiving-end grid voltage stability. |
---|---|
ISSN: | 1742-6588 1742-6596 |