Analysis of Short-Circuit Fault Current Characteristics on AC Side of Wind-PV-Storage Integrated Grid Connected System

Abstract The penetration rate of Wind-Soloar-Storage integrated grid-connected systems in the power grid is getting higher and higher. However, the mechanism of its influence on the short-circuit current is still not deeply understood. This paper analyzes the low-voltage ride-through and reactive po...

Full description

Saved in:
Bibliographic Details
Published inJournal of physics. Conference series Vol. 2503; no. 1; pp. 12014 - 12022
Main Authors Cheng, Xiaoping, Tang, Xiaojun, Huo, Qidi, Xie, Yan, Wang, Ziqi, Gao, Wenman
Format Journal Article
LanguageEnglish
Published Bristol IOP Publishing 01.05.2023
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:Abstract The penetration rate of Wind-Soloar-Storage integrated grid-connected systems in the power grid is getting higher and higher. However, the mechanism of its influence on the short-circuit current is still not deeply understood. This paper analyzes the low-voltage ride-through and reactive power compensation strategies of a Wind-PV-Storage integrated grid-connected system; the short-circuit process of the AC side is studied, and the voltage sag degree and limiting link affect the steady amplitude and phase of the current. Through establishing the Wind-PV-Storage integrated grid connected system model in PSCAD/EMTDC, theoretical analysis and verification are carried out on the influence of factors such as the collection line inside the station and different capacity distribution proportions of the station on the short-circuit current.
ISSN:1742-6588
1742-6596
DOI:10.1088/1742-6596/2503/1/012014