Increasing the Reliablity of the Measuring Circuits of Protection Relays
The primary current of a current transformer (CT) is calculated on the basis of the characteristics of the magnetization and the measured secondary current of the CT. This makes it possible to extend the linear range of operation of the measuring circuit of the protection and thereby increase the pr...
Saved in:
Published in | Power technology and engineering Vol. 50; no. 1; pp. 87 - 92 |
---|---|
Main Authors | , , , |
Format | Journal Article |
Language | English |
Published |
New York
Springer US
01.05.2016
|
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | The primary current of a current transformer (CT) is calculated on the basis of the characteristics of the magnetization and the measured secondary current of the CT. This makes it possible to extend the linear range of operation of the measuring circuit of the protection and thereby increase the protection stability. The mathematical model of a current transformer and the reset algorithm for the primary and magnetization currents are described and the operation of the algorithm in different transient processes is analyzed. |
---|---|
ISSN: | 1570-145X 1570-1468 |
DOI: | 10.1007/s10749-016-0665-z |