The use of Markov Chain method to determine spare transformer number and location
The purpose of this study is to develop a method to determine spare transformer number and location. Using Markov Chain method, state transition model and steady state probability was used on each 500-kV substation in order to analyze the effect of spare number and location variation with the reliab...
Saved in:
Published in | International journal of electrical and computer engineering (Malacca, Malacca) Vol. 9; no. 1; p. 1 |
---|---|
Main Authors | , , |
Format | Journal Article |
Language | English |
Published |
Yogyakarta
IAES Institute of Advanced Engineering and Science
01.02.2019
|
Subjects | |
Online Access | Get full text |
Cover
Loading…
Summary: | The purpose of this study is to develop a method to determine spare transformer number and location. Using Markov Chain method, state transition model and steady state probability was used on each 500-kV substation in order to analyze the effect of spare number and location variation with the reliability changes. To give an actual result of the case study, calculation of spare transformer number and location on 500/150 kV transformers in Java Bali System was analyzed. The steady state probability results will vary depending on the number of spare transformer, these results can then be used to assess the spare transformer needed. The variation of spare transformer location can be used to analyze the best possible location of the spare in order to satisfy the reliability required. The methodology presented shows an integrated calculation for determining the spare transformer number and location. |
---|---|
ISSN: | 2088-8708 2088-8708 |
DOI: | 10.11591/ijece.v9i1.pp1-13 |