Effect of O 2 on AC Partial Discharge and Decomposition Behavior of C 4 F 7 N/CO 2 /O 2 Gas Mixture

This paper focus on the influence of oxygen on the partial discharge (PD) and decomposition characteristics of C 4 F 7 N/CO 2 /O 2 gas mixture as eco-friendly gas insulating medium. The PD characteristic parameters and phase resolved partial discharge (PRPD) patterns of C 4 F 7 N/CO 2 /O 2 gas mixtu...

Full description

Saved in:
Bibliographic Details
Published inIEEE transactions on dielectrics and electrical insulation Vol. 28; no. 4; pp. 1440 - 1448
Main Authors Ye, Fanchao, Zhang, Xiaoxing, Li, Yi, Yao, Yuhang, Xiao, Song, Xie, Cheng, Shao, Xianjun, Sun, Xiang
Format Journal Article
LanguageEnglish
Published New York The Institute of Electrical and Electronics Engineers, Inc. (IEEE) 01.08.2021
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:This paper focus on the influence of oxygen on the partial discharge (PD) and decomposition characteristics of C 4 F 7 N/CO 2 /O 2 gas mixture as eco-friendly gas insulating medium. The PD characteristic parameters and phase resolved partial discharge (PRPD) patterns of C 4 F 7 N/CO 2 /O 2 gas mixture are, respectively, extracted and constructed. The influences of oxygen content and applied voltage on the PD and decomposition characteristics of C 4 F 7 N/CO 2 /O 2 gas mixture are investigated based on gas chromatography-mass spectrometry (GC-MS). We find that the addition of 2-4% O 2 to C 4 F 7 N/CO 2 gas mixture can significantly inhibit the negative half-cycle PDs and the generation of most by-products (CF 4 , C 2 F 6 , C 3 F 6 , CO, C 2 F 6 O 3 , CF 3 CN, C 2 F 5 CN, C 2 N 2 ). With the oxygen content higher than 6%, the accumulation discharge magnitude and discharge repetition rates of C 4 F 7 N/CO 2 /O 2 gas mixture increase sharply, accompanying the intensification of decomposition and deterioration of insulation strength. There is a positive correlation between the mean discharge magnitude and gas mixture decomposition intensity. To avoid the serious impact of PD fault on gas insulated equipment (GIE), the optimal oxygen addition in C 4 F 7 N/CO 2 /O 2 gas mixture should not exceed 6%.
ISSN:1070-9878
1558-4135
DOI:10.1109/TDEI.2021.009626