HARMONIC STUDY OF VFDS AND FILTER DESIGN: A CASE STUDY FOR SUGAR INDUSTRY WITH COGENERATION

In majority of sugar industries, to achieve better efficiency of power, VFDs are extensively used. Initially D.C. Drives were used, but now these are slowly getting phased out and are replaced by A.C. Drives. In a case study of Harmonic Analysis of SAMARTH CO-OPERATIVE SUGAR FACTORY, ANKUSH NAGAR, M...

Full description

Saved in:
Bibliographic Details
Published inInternational journal of advances in engineering and technology Vol. 7; no. 3; p. 782
Main Authors Gosavi, V P, Shinde, S M
Format Journal Article
LanguageEnglish
Published Bareilly I A E T Publishing Company 01.07.2014
Subjects
Online AccessGet full text

Cover

Loading…
More Information
Summary:In majority of sugar industries, to achieve better efficiency of power, VFDs are extensively used. Initially D.C. Drives were used, but now these are slowly getting phased out and are replaced by A.C. Drives. In a case study of Harmonic Analysis of SAMARTH CO-OPERATIVE SUGAR FACTORY, ANKUSH NAGAR, MAHAKALA, JALNA, it is commonly seen perception that the latest technology A.C. drives are having in built harmonic filters and hence do not produce harmonics/produce harmonics within prescribed tolerance limit. Because of variation in load pattern these drives still produce harmonics, which must be suppressed by using appropriate Harmonic Filter, otherwise, it may result into malfunction of sensitive devices. It is more essential to suppress these harmonics, for SAMARTH CO-OPERATIVE SUGAR FACTORY, ANKUSH NAGAR, MAHAKALA, JALNA, as sugar industry has grid connected cogeneration plant. The suggested method of filter design gives better result, reduces harmonic level (5th harmonics) to almost 10A from 154A.
Bibliography:ObjectType-Article-1
SourceType-Scholarly Journals-1
ObjectType-Feature-2
content type line 23
ISSN:2231-1963
2231-1963