A review of thermal management and innovative cooling strategies for data center

•Review of existing cooling technologies of data centers.•Analysis of energy consumption and energy savings of data centers.•Performance of various innovative future cooling technologies for high efficiency is studied. Within a data center, 52% of the electricity is used by the IT equipment, 38% by...

Full description

Saved in:
Bibliographic Details
Published inSustainable computing informatics and systems Vol. 19; pp. 14 - 28
Main Authors Nadjahi, Chayan, Louahlia, Hasna, Lemasson, Stéphane
Format Journal Article
LanguageEnglish
Published Elsevier Inc 01.09.2018
Elsevier
Subjects
Online AccessGet full text
ISSN2210-5379
DOI10.1016/j.suscom.2018.05.002

Cover

Loading…
Abstract •Review of existing cooling technologies of data centers.•Analysis of energy consumption and energy savings of data centers.•Performance of various innovative future cooling technologies for high efficiency is studied. Within a data center, 52% of the electricity is used by the IT equipment, 38% by the cooling system, and 10% for the remaining equipment (electrical power distribution, UPS…). The cooling system is mandatory to maintain optimal air temperature and relative humidity and provide a safe environment for all the electronic equipment. This paper presents a review on thermal management in data centers and various potential cooling technologies developed respecting energy saving constraint. Numerous researchers have proposed different alternative cooling strategy and solutions to free air cooling. This article describes a state of the art cooling strategies of data centers. The open aisle configuration is the most often used technique to remove heat. It does not affect energy efficiency but increases the electricity consumption dedicated to air conditioning. The most promising cooling systems, capable of absorbing energy flux while decreasing electricity consumption and rising the energy efficiency, are identified and discussed. It includes free cooling, liquid cooling, two-phase technologies and building envelope.
AbstractList •Review of existing cooling technologies of data centers.•Analysis of energy consumption and energy savings of data centers.•Performance of various innovative future cooling technologies for high efficiency is studied. Within a data center, 52% of the electricity is used by the IT equipment, 38% by the cooling system, and 10% for the remaining equipment (electrical power distribution, UPS…). The cooling system is mandatory to maintain optimal air temperature and relative humidity and provide a safe environment for all the electronic equipment. This paper presents a review on thermal management in data centers and various potential cooling technologies developed respecting energy saving constraint. Numerous researchers have proposed different alternative cooling strategy and solutions to free air cooling. This article describes a state of the art cooling strategies of data centers. The open aisle configuration is the most often used technique to remove heat. It does not affect energy efficiency but increases the electricity consumption dedicated to air conditioning. The most promising cooling systems, capable of absorbing energy flux while decreasing electricity consumption and rising the energy efficiency, are identified and discussed. It includes free cooling, liquid cooling, two-phase technologies and building envelope.
Author Nadjahi, Chayan
Lemasson, Stéphane
Louahlia, Hasna
Author_xml – sequence: 1
  givenname: Chayan
  surname: Nadjahi
  fullname: Nadjahi, Chayan
  organization: NORMANDIE UNIV, UNICAEN, LUSAC, Site universitaire Bellevue, 120 rue de l’Exode, 50000 Saint-Lô, France
– sequence: 2
  givenname: Hasna
  surname: Louahlia
  fullname: Louahlia, Hasna
  email: hasna.louahlia@unicaen.fr
  organization: NORMANDIE UNIV, UNICAEN, LUSAC, Site universitaire Bellevue, 120 rue de l’Exode, 50000 Saint-Lô, France
– sequence: 3
  givenname: Stéphane
  surname: Lemasson
  fullname: Lemasson, Stéphane
  organization: Orange Labs, 2, avenue Pierre Marzin, 22307 Lannion, France
BackLink https://normandie-univ.hal.science/hal-02165699$$DView record in HAL
BookMark eNqFkLFOwzAQhj0UiQJ9AwavDAm247gNA1JVAUWqBAPMlmNfWleJjWxTxNvjKoiBAW456e7_TrrvDE2cd4DQJSUlJVRc78v4HrUfSkbooiR1SQiboCljlBR1NW9O0SzGPclVC9pUfIqelzjAwcIH9h1OOwiD6vGgnNrCAC5h5Qy2zvmDSvYAWHvfW7fFMQWVYGsh4s4HbFRSWOc8hAt00qk-wuy7n6PX-7uX1brYPD08rpabQlecpIIb1rCuBSH0nAimhWmhErStOOW1og3VptN0bjgTvFVNu1DczBu9qIiqWd5V5-hqvLtTvXwLdlDhU3pl5Xq5kccZYVTUomkONGf5mNXBxxig-wEokUdxci9HcfIoTpJaZnEZu_mFaZuyB-_y97b_D74dYcgSsuAgo7bgNBgbQCdpvP37wBdJLpCb
CitedBy_id crossref_primary_10_1016_j_enbuild_2021_110764
crossref_primary_10_1007_s11365_024_01019_8
crossref_primary_10_1021_acsaom_3c00235
crossref_primary_10_1145_3700874
crossref_primary_10_1016_j_csite_2023_103262
crossref_primary_10_1016_j_enbuild_2020_110407
crossref_primary_10_1109_TSUSC_2023_3346332
crossref_primary_10_3389_fenrg_2024_1449358
crossref_primary_10_1063_5_0190273
crossref_primary_10_1109_ACCESS_2019_2932777
crossref_primary_10_12677_mos_2024_134440
crossref_primary_10_32604_EE_2022_017356
crossref_primary_10_1016_j_applthermaleng_2024_124952
crossref_primary_10_1051_matecconf_202032803008
crossref_primary_10_1615_JEnhHeatTransf_2022041591
crossref_primary_10_1051_e3sconf_201911101043
crossref_primary_10_1007_s10853_022_06945_y
crossref_primary_10_1016_j_aeue_2019_153040
crossref_primary_10_15377_2409_5826_2019_06_3
crossref_primary_10_59717_j_xinn_energy_2024_100014
crossref_primary_10_1007_s10973_023_12203_3
crossref_primary_10_1177_1420326X231183300
crossref_primary_10_1088_1755_1315_1372_1_012090
crossref_primary_10_1063_5_0176286
crossref_primary_10_1007_s11708_023_0912_6
crossref_primary_10_1016_j_rser_2021_111389
crossref_primary_10_1155_2022_9051629
crossref_primary_10_18686_cest_v2i1_141
crossref_primary_10_1109_TIA_2024_3379305
crossref_primary_10_1080_15435075_2021_2016415
crossref_primary_10_1515_nanoph_2022_0089
crossref_primary_10_1080_08916152_2023_2273812
crossref_primary_10_1063_5_0138916
crossref_primary_10_1109_ACCESS_2019_2907701
crossref_primary_10_1109_TIA_2021_3054607
crossref_primary_10_1016_j_apenergy_2022_120539
crossref_primary_10_1109_TCPMT_2021_3117572
crossref_primary_10_4028_p_LwToX6
crossref_primary_10_1016_j_ijheatmasstransfer_2021_121925
crossref_primary_10_1016_j_enconman_2021_113983
crossref_primary_10_1016_j_applthermaleng_2024_124775
crossref_primary_10_1088_1742_6596_1402_4_044057
crossref_primary_10_1016_j_applthermaleng_2023_121260
crossref_primary_10_1287_msom_2022_1178
crossref_primary_10_36887_2415_8453_2024_2_23
crossref_primary_10_1007_s11227_021_03805_5
crossref_primary_10_1186_s40807_024_00120_4
crossref_primary_10_1016_j_jobe_2024_108644
crossref_primary_10_1109_ACCESS_2023_3292342
crossref_primary_10_1155_2020_5934747
crossref_primary_10_1360_SST_2022_0155
crossref_primary_10_1007_s40430_024_05048_w
crossref_primary_10_1016_j_apenergy_2019_114109
crossref_primary_10_1016_j_applthermaleng_2024_122425
crossref_primary_10_1109_TCC_2024_3521666
crossref_primary_10_2298_TSCI230311175K
crossref_primary_10_1016_j_applthermaleng_2025_125476
crossref_primary_10_3389_fenrg_2022_954718
crossref_primary_10_1016_j_aej_2022_02_059
Cites_doi 10.1016/j.enconman.2013.07.035
10.1016/j.rser.2013.12.007
10.1016/j.applthermaleng.2015.07.078
10.1016/j.enbuild.2010.05.008
10.1016/j.rser.2016.03.036
10.1016/j.energy.2012.04.037
10.1016/j.applthermaleng.2011.12.008
10.1016/j.applthermaleng.2012.05.023
10.1109/TCPMT.2012.2185797
10.1016/j.scs.2017.10.012
10.1016/j.rser.2012.01.038
10.1007/s10619-006-7007-3
10.1016/j.egypro.2015.12.168
10.1016/j.applthermaleng.2015.12.020
10.1016/j.ijheatmasstransfer.2005.06.028
10.1016/j.applthermaleng.2005.11.001
10.1016/j.expthermflusci.2008.12.006
10.1016/j.mcm.2011.06.047
10.1016/j.energy.2011.02.021
10.1016/j.enconman.2015.01.088
10.1016/j.egypro.2011.12.985
10.1016/j.ijrefrig.2012.09.012
10.1016/j.applthermaleng.2014.09.060
10.1016/j.rser.2014.04.017
10.1016/j.ijheatmasstransfer.2010.02.039
10.1016/j.enbuild.2012.08.012
10.1016/j.apenergy.2011.02.003
10.1016/j.enbuild.2012.03.040
10.1016/j.apenergy.2013.12.010
10.1016/j.ijheatmasstransfer.2012.02.063
ContentType Journal Article
Copyright 2018 Elsevier Inc.
Distributed under a Creative Commons Attribution 4.0 International License
Copyright_xml – notice: 2018 Elsevier Inc.
– notice: Distributed under a Creative Commons Attribution 4.0 International License
DBID AAYXX
CITATION
1XC
DOI 10.1016/j.suscom.2018.05.002
DatabaseName CrossRef
Hyper Article en Ligne (HAL)
DatabaseTitle CrossRef
DatabaseTitleList
DeliveryMethod fulltext_linktorsrc
Discipline Computer Science
EndPage 28
ExternalDocumentID oai_HAL_hal_02165699v1
10_1016_j_suscom_2018_05_002
S2210537917304067
GroupedDBID --K
--M
.~1
0R~
1~.
4.4
457
4G.
7-5
8P~
AACTN
AAEDT
AAEDW
AAHCO
AAIAV
AAIKJ
AAKOC
AALRI
AAOAW
AARJD
AAXUO
AAYFN
ABBOA
ABMAC
ABXDB
ABYKQ
ACDAQ
ACGFS
ACNNM
ACRLP
ACZNC
ADBBV
ADEZE
ADMUD
AEBSH
AEKER
AFKWA
AFTJW
AGHFR
AGUBO
AGYEJ
AHZHX
AIALX
AIEXJ
AIKHN
AITUG
AJBFU
AJOXV
ALMA_UNASSIGNED_HOLDINGS
AMFUW
AMRAJ
AOUOD
AXJTR
BELTK
BKOJK
BLXMC
EBS
EFJIC
EFLBG
EJD
FDB
FIRID
FNPLU
FYGXN
GBLVA
GBOLZ
HZ~
J1W
JARJE
KOM
M41
MO0
N9A
O-L
O9-
OAUVE
P-8
P-9
PC.
Q38
RIG
ROL
SDF
SES
SPC
SPCBC
SSR
SSV
SSZ
T5K
~G-
AAQFI
AATTM
AAXKI
AAYWO
AAYXX
ABJNI
ABWVN
ACRPL
ADNMO
AEIPS
AFJKZ
AFXIZ
AGCQF
AGRNS
AIIUN
ANKPU
APXCP
BNPGV
CITATION
SSH
1XC
ID FETCH-LOGICAL-c340t-4d292fbe66c7062c6dbe361b34145a191cdfc17d4264ba9b8a4d79c830a52cdf3
IEDL.DBID .~1
ISSN 2210-5379
IngestDate Fri May 09 12:11:28 EDT 2025
Tue Jul 01 01:35:18 EDT 2025
Thu Apr 24 23:05:00 EDT 2025
Fri Feb 23 02:26:31 EST 2024
IsPeerReviewed false
IsScholarly true
Keywords Cooling technologies
Thermal management
Data center
Energy efficiency
Language English
License Distributed under a Creative Commons Attribution 4.0 International License: http://creativecommons.org/licenses/by/4.0
LinkModel DirectLink
MergedId FETCHMERGED-LOGICAL-c340t-4d292fbe66c7062c6dbe361b34145a191cdfc17d4264ba9b8a4d79c830a52cdf3
ORCID 0000-0003-3197-7511
PageCount 15
ParticipantIDs hal_primary_oai_HAL_hal_02165699v1
crossref_primary_10_1016_j_suscom_2018_05_002
crossref_citationtrail_10_1016_j_suscom_2018_05_002
elsevier_sciencedirect_doi_10_1016_j_suscom_2018_05_002
ProviderPackageCode CITATION
AAYXX
PublicationCentury 2000
PublicationDate September 2018
2018-09-00
2018-09
PublicationDateYYYYMMDD 2018-09-01
PublicationDate_xml – month: 09
  year: 2018
  text: September 2018
PublicationDecade 2010
PublicationTitle Sustainable computing informatics and systems
PublicationYear 2018
Publisher Elsevier Inc
Elsevier
Publisher_xml – name: Elsevier Inc
– name: Elsevier
References Nemec, Čaja, Malcho (bib0185) 2013; 57
Sun, Zhang, Medina, Liu, Liao (bib0245) 2014; 117
Zimmermann, Meijer, Tiwari, Paredes, Michel, Poulikakos (bib0145) 2012; 43
Almaneea, Thompson, Summers, Kapur (bib0220) 2014; 4
Ebrahimi, Jones, Fleischer (bib0005) 2014; 31
Singhal, Litke, Black, Garimella (bib0090) 2005; 48
Haywood, Sherbeck, Phelan, Varsamopoulos, Gupta (bib0155) 2015; 95
Power Emerson Network (bib0080) 2007
Dunnavant, Rejection (bib0125) 2011
Samba, Louahlia-Gualous, Le Masson, Nörterhäuser (bib0170) 2013; 50
Oró, Allepuz, Martorell, Salom (bib0265) 2018; 36
Tschudi, Berkeley (bib0045) 2010
Valiorgue, Persoons, McGuinn, Murray (bib0165) 2009; 33
J. Niemann, K. Brown, and V. Avelar, Impact of Hot and Cold Aisle Containment on Data Center Temperature and Efficiency.
Bao, Wang, Kang (bib0130) 2012; 14
Sundaram, Seeniraj, Velraj (bib0250) 2010; 42
H. Jouhara and R. Meskimmon, Heat Pipe based Thermal Management Systems for Energy-Efficient Data Centres.
Petit (bib0215) 2008; 33
Potts (bib0110) 2010
Ashrae (bib0075) 2011
Singh, Mochizuki, Mashiko, Nguyen (bib0190) 2011; 36
Marcinichen, Olivier, Thome (bib0065) 2012; 41
Chen, Zhang, Meng (bib0115) 2012; 50
Kaiser, Bean, Harvey, Patterson, Winiecki (bib0255) 2011
Zhang, Shao, Xu, Zou, Tian (bib0200) 2015; 75
Akeiber (bib0240) 2016; 60
Harirchian, Garimella (bib0095) 2010; 53
Garday (bib0260) 2007
Nada, Said, Rady (bib0010) 2016; 98
Han, Shi, Wang, Zhang, Li (bib0205) 2013; 36
ETSI (bib0070) 2009; vol. 2
Ling, Zhang, Yu, Wu, Liao (bib0195) 2015; vol. 59
Cho, Lim, Sean (bib0020) 2012; 55
Capozzoli, Primiceri (bib0135) 2015; 83
Chaudhry, Hughes, Ghani (bib0175) 2012; 16
Endo, Kodama, Fukuda, Sugimoto, Horie, Kondo (bib0235) 2013; 6
Niemann, Bean, Avelar (bib0120) 2013
Koomey (bib0030) 2010
The Green Grid (bib0040) 2007
Baonga, Louahlia-Gualous, Imbert (bib0160) 2006; 26
Brady, Kapur, Summers, Thompson (bib0050) 2013; 76
Rambo, Joshi (bib0060) 2007; 21
Zhang, Shao, Xu, Zou, Tian (bib0105) 2014; 35
Greenberg, Mills, Tschudi, Berkeley (bib0055) 2006; sUMMER
Garimella, Yeh, Persoons (bib0025) 2012; 2
Warrier, Sathyanarayana, Patil, France, Joshi, Teja (bib0225) 2012; 55
The Climate Group (bib0035) 2008; 30
Almoli, Thompson, Kapur, Summers, Thompson, Hannah (bib0150) 2012; 89
“Bicsi.” [Online]. Available: https://www.bicsi.org/uploadedfiles/BICSI_Summits/Spring2/balt_11/Passive Air Flow Management in the Data Center - Lylette Macdonald - Legrand-Ortronics.pdf.
Douchet (bib0015) 2015
Wang, Zhang, Li, Luo (bib0210) 2015; 90
Li, Zheng, Wang, Wang (bib0140) 2014
Tuma (bib0230) 2010
Zhang (10.1016/j.suscom.2018.05.002_bib0200) 2015; 75
Zimmermann (10.1016/j.suscom.2018.05.002_bib0145) 2012; 43
Dunnavant (10.1016/j.suscom.2018.05.002_bib0125) 2011
Garimella (10.1016/j.suscom.2018.05.002_bib0025) 2012; 2
Brady (10.1016/j.suscom.2018.05.002_bib0050) 2013; 76
Garday (10.1016/j.suscom.2018.05.002_bib0260) 2007
Singh (10.1016/j.suscom.2018.05.002_bib0190) 2011; 36
Niemann (10.1016/j.suscom.2018.05.002_bib0120) 2013
Greenberg (10.1016/j.suscom.2018.05.002_bib0055) 2006; sUMMER
Marcinichen (10.1016/j.suscom.2018.05.002_bib0065) 2012; 41
10.1016/j.suscom.2018.05.002_bib0085
Almoli (10.1016/j.suscom.2018.05.002_bib0150) 2012; 89
Sundaram (10.1016/j.suscom.2018.05.002_bib0250) 2010; 42
Tschudi (10.1016/j.suscom.2018.05.002_bib0045) 2010
Potts (10.1016/j.suscom.2018.05.002_bib0110) 2010
Chaudhry (10.1016/j.suscom.2018.05.002_bib0175) 2012; 16
Petit (10.1016/j.suscom.2018.05.002_bib0215) 2008; 33
Sun (10.1016/j.suscom.2018.05.002_bib0245) 2014; 117
Akeiber (10.1016/j.suscom.2018.05.002_bib0240) 2016; 60
Warrier (10.1016/j.suscom.2018.05.002_bib0225) 2012; 55
Valiorgue (10.1016/j.suscom.2018.05.002_bib0165) 2009; 33
Ebrahimi (10.1016/j.suscom.2018.05.002_bib0005) 2014; 31
Koomey (10.1016/j.suscom.2018.05.002_bib0030) 2010
The Green Grid (10.1016/j.suscom.2018.05.002_bib0040) 2007
Harirchian (10.1016/j.suscom.2018.05.002_bib0095) 2010; 53
Oró (10.1016/j.suscom.2018.05.002_bib0265) 2018; 36
The Climate Group (10.1016/j.suscom.2018.05.002_bib0035) 2008; 30
Haywood (10.1016/j.suscom.2018.05.002_bib0155) 2015; 95
Samba (10.1016/j.suscom.2018.05.002_bib0170) 2013; 50
Power Emerson Network (10.1016/j.suscom.2018.05.002_bib0080) 2007
Nemec (10.1016/j.suscom.2018.05.002_bib0185) 2013; 57
Almaneea (10.1016/j.suscom.2018.05.002_bib0220) 2014; 4
Singhal (10.1016/j.suscom.2018.05.002_bib0090) 2005; 48
Li (10.1016/j.suscom.2018.05.002_bib0140) 2014
Rambo (10.1016/j.suscom.2018.05.002_bib0060) 2007; 21
ETSI (10.1016/j.suscom.2018.05.002_bib0070) 2009; vol. 2
Baonga (10.1016/j.suscom.2018.05.002_bib0160) 2006; 26
Capozzoli (10.1016/j.suscom.2018.05.002_bib0135) 2015; 83
Wang (10.1016/j.suscom.2018.05.002_bib0210) 2015; 90
Zhang (10.1016/j.suscom.2018.05.002_bib0105) 2014; 35
Cho (10.1016/j.suscom.2018.05.002_bib0020) 2012; 55
Bao (10.1016/j.suscom.2018.05.002_bib0130) 2012; 14
Nada (10.1016/j.suscom.2018.05.002_bib0010) 2016; 98
10.1016/j.suscom.2018.05.002_bib0180
Ashrae (10.1016/j.suscom.2018.05.002_bib0075) 2011
Chen (10.1016/j.suscom.2018.05.002_bib0115) 2012; 50
Endo (10.1016/j.suscom.2018.05.002_bib0235) 2013; 6
Tuma (10.1016/j.suscom.2018.05.002_bib0230) 2010
Kaiser (10.1016/j.suscom.2018.05.002_bib0255) 2011
Ling (10.1016/j.suscom.2018.05.002_bib0195) 2015; vol. 59
Douchet (10.1016/j.suscom.2018.05.002_bib0015) 2015
10.1016/j.suscom.2018.05.002_bib0100
Han (10.1016/j.suscom.2018.05.002_bib0205) 2013; 36
References_xml – volume: 21
  start-page: 193
  year: 2007
  end-page: 225
  ident: bib0060
  article-title: Modeling of data center airflow and heat transfer: state of the art and future trends
  publication-title: Distrib. Parallel Databases
– volume: 30
  start-page: 1
  year: 2008
  end-page: 87
  ident: bib0035
  article-title: SMART 2020: enabling the low carbon economy in the information age
  publication-title: Group
– reference: H. Jouhara and R. Meskimmon, Heat Pipe based Thermal Management Systems for Energy-Efficient Data Centres.
– volume: 4
  start-page: 200
  year: 2014
  end-page: 207
  ident: bib0220
  article-title: Cooling system analysis for a data center using liquid immersed servers
  publication-title: Int. J. Therm. Technol.
– volume: 36
  start-page: 185
  year: 2018
  end-page: 203
  ident: bib0265
  article-title: Design and economic analysis of liquid cooled data centres for waste heat recovery: a case study for an indoor swimming pool
  publication-title: Sustain. Cities Soc.
– volume: 16
  start-page: 2249
  year: 2012
  end-page: 2259
  ident: bib0175
  article-title: A review of heat pipe systems for heat recovery and renewable energy applications
  publication-title: Renew. Sustain. Energy Rev.
– year: 2007
  ident: bib0260
  article-title: Reducing Data Center Energy Consumption With Wet Side Economizers
– year: 2015
  ident: bib0015
  article-title: Optimisation énergétique de data centers par utilisation de liquides pour le refroidissement des baies informatiques
– volume: 31
  start-page: 622
  year: 2014
  end-page: 638
  ident: bib0005
  article-title: A review of data center cooling technology, operating conditions and the corresponding low-grade waste heat recovery opportunities
  publication-title: Renew. Sustain. Energy Rev.
– reference: J. Niemann, K. Brown, and V. Avelar, Impact of Hot and Cold Aisle Containment on Data Center Temperature and Efficiency.
– volume: 43
  start-page: 237
  year: 2012
  end-page: 245
  ident: bib0145
  article-title: Aquasar: a hot water cooled data center with direct energy reuse
  publication-title: Energy
– volume: 50
  start-page: 1351
  year: 2013
  end-page: 1360
  ident: bib0170
  article-title: Two-phase thermosyphon loop for cooling outdoor telecommunication equipments
  publication-title: Appl. Therm. Eng.
– volume: sUMMER
  start-page: 76
  year: 2006
  end-page: 87
  ident: bib0055
  article-title: Best practices for data centers: lessons learned from benchmarking 22 data centers T
  publication-title: Aceee
– volume: 6
  start-page: 17
  year: 2013
  end-page: 25
  ident: bib0235
  article-title: Effect of climatic conditions on energy consumption in direct fresh-air container data centers 2013
  publication-title: 2013 Int. Green Comput. Conf. Proceedings, IGCC
– volume: 57
  start-page: 126
  year: 2013
  end-page: 136
  ident: bib0185
  article-title: Mathematical model for heat transfer limitations of heat pipe
  publication-title: Math. Comput. Model.
– volume: 41
  start-page: 36
  year: 2012
  end-page: 51
  ident: bib0065
  article-title: On-chip two-phase cooling of datacenters: cooling system and energy recovery evaluation
  publication-title: Appl. Therm. Eng.
– year: 2010
  ident: bib0045
  article-title: Ere: a metric for measuring the benefit of reuse energy from a editor
  publication-title: Star
– volume: 95
  start-page: 297
  year: 2015
  end-page: 303
  ident: bib0155
  article-title: The relationship among CPU utilization, temperature, and thermal power for waste heat utilization
  publication-title: Energy Convers. Manag.
– volume: 36
  start-page: 58
  year: 2013
  end-page: 69
  ident: bib0205
  article-title: Development of an integrated air conditioner with thermosyphon and the application in mobile phone base station
  publication-title: Int. J. Refrig.
– volume: vol. 2
  start-page: 1
  year: 2009
  end-page: 21
  ident: bib0070
  publication-title: ETSI EN 300 019-1-3 V2.3.2, Equipment Engineering(EE); Environmental Conditions and Environmnetal Tests for Telecommunications Equipment; Part 1-3: Classification of Environmental Conditions; Stationary Use at Weatherprotected Locations
– volume: 89
  start-page: 150
  year: 2012
  end-page: 155
  ident: bib0150
  article-title: Computational fluid dynamic investigation of liquid rack cooling in data centres
  publication-title: Appl. Energy
– volume: 26
  start-page: 1125
  year: 2006
  end-page: 1138
  ident: bib0160
  article-title: Experimental study of the hydrodynamic and heat transfer of free liquid jet impinging a flat circular heated disk
  publication-title: Appl. Therm. Eng.
– start-page: 1
  year: 2011
  end-page: 19
  ident: bib0255
  article-title: Survey Results: Data Center Economizer Use
– volume: 90
  start-page: 937
  year: 2015
  end-page: 944
  ident: bib0210
  article-title: Analysis on energy efficiency of an integrated heat pipe system in data centers
  publication-title: Appl. Therm. Eng.
– volume: 76
  start-page: 155
  year: 2013
  end-page: 161
  ident: bib0050
  article-title: A case study and critical assessment in calculating power usage effectiveness for a data centre
  publication-title: Energy Convers. Manag.
– volume: 14
  start-page: 620
  year: 2012
  end-page: 625
  ident: bib0130
  article-title: The applied effect analysis of heat exchanger installed in a typical communication base station in Beijing of China
  publication-title: Energy Procedia
– start-page: 249
  year: 2014
  end-page: 259
  ident: bib0140
  article-title: Coordinating liquid and free air cooling with workload allocation for data center power minimization
  publication-title: 11th Int. Conf. Auton. Comput. (ICAC 14)
– volume: 50
  start-page: 212
  year: 2012
  end-page: 218
  ident: bib0115
  article-title: Study of ventilation cooling technology for telecommunication base stations: control strategy and application strategy
  publication-title: Energy Build.
– start-page: 1
  year: 2011
  end-page: 45
  ident: bib0075
  article-title: Thermal guidelines for data processing environments – expanded data center
  publication-title: Data Process.
– volume: 33
  start-page: 1
  year: 2008
  end-page: 16
  ident: bib0215
  article-title: Dissipation thermique dans les systèmes électroniques
  publication-title: Tech. l’Ingénieur
– volume: 117
  start-page: 95
  year: 2014
  end-page: 103
  ident: bib0245
  article-title: A study on the use of phase change materials (PCMs) in combination with a natural cold source for space cooling in telecommunications base stations (TBSs) in China
  publication-title: Appl. Energy
– volume: 2
  start-page: 1307
  year: 2012
  end-page: 1316
  ident: bib0025
  article-title: Thermal management challenges in telecommunication systems and data centers
  publication-title: IEEE Trans. Componen. Packag. Manuf. Technol.
– year: 2013
  ident: bib0120
  article-title: Economizer Modes of Data Center Cooling Systems
– volume: vol. 59
  start-page: 198
  year: 2015
  end-page: 209
  ident: bib0195
  publication-title: Study on thermal performance of micro-channel separate heat pipe for telecommunication stations : Experiment and simulation Étude de la performance thermique de caloduc séparé à micro-canaux pour les stations de télécommunication : expérienc
– volume: 83
  start-page: 484
  year: 2015
  end-page: 493
  ident: bib0135
  article-title: Cooling systems in data centers: state of art and emerging technologies
  publication-title: Energy Procedia
– volume: 60
  start-page: 1470
  year: 2016
  end-page: 1497
  ident: bib0240
  article-title: A review on phase change material (PCM) for sustainable passive cooling in building envelopes
  publication-title: Renew. Sustain. Energy Rev.
– volume: 42
  start-page: 1726
  year: 2010
  end-page: 1735
  ident: bib0250
  article-title: An experimental investigation on passive cooling system comprising phase change material and two-phase closed thermosyphon for telecom shelters in tropical and desert regions
  publication-title: Energy Build.
– volume: 53
  start-page: 2694
  year: 2010
  end-page: 2702
  ident: bib0095
  article-title: A comprehensive flow regime map for microchannel flow boiling with quantitative transition criteria
  publication-title: Int. J. Heat. Mass. Transf.
– volume: 55
  start-page: 3379
  year: 2012
  end-page: 3385
  ident: bib0225
  article-title: Novel heat transfer fluids for direct immersion phase change cooling of electronic systems
  publication-title: Int. J. Heat. Mass. Transf.
– volume: 55
  start-page: 189
  year: 2012
  end-page: 197
  ident: bib0020
  article-title: Viability of datacenter cooling systems for energy efficiency in temperate or subtropical regions : case study
  publication-title: Energy Build.
– year: 2010
  ident: bib0110
  article-title: Free Cooling Technologies in Data Centre Applications
– volume: 35
  start-page: 171
  year: 2014
  end-page: 182
  ident: bib0105
  article-title: Free cooling of data centers: a review
  publication-title: Renew. Sustain. Energy Rev.
– year: 2011
  ident: bib0125
  publication-title: ASHRAE J.
– start-page: 123
  year: 2010
  end-page: 131
  ident: bib0230
  article-title: The merits of open bath immersion cooling of datacom equipment April
  publication-title: Annu. IEEE Semicond. Therm. Meas. Manag. Symp.
– reference: “Bicsi.” [Online]. Available: https://www.bicsi.org/uploadedfiles/BICSI_Summits/Spring2/balt_11/Passive Air Flow Management in the Data Center - Lylette Macdonald - Legrand-Ortronics.pdf.
– year: 2007
  ident: bib0040
  article-title: Green Grid Metrics: Describing Data Center Power Efficiency
– volume: 75
  start-page: 185
  year: 2015
  end-page: 192
  ident: bib0200
  article-title: Integrated system of mechanical refrigeration and thermosyphon for free cooling of data centers
  publication-title: Appl. Therm. Eng.
– volume: 48
  start-page: 5446
  year: 2005
  end-page: 5459
  ident: bib0090
  article-title: An experimentally validated thermo-mechanical model for the prediction of thermal contact conductance
  publication-title: Int. J. Heat. Mass. Transf.
– year: 2010
  ident: bib0030
  article-title: Growth in Data Center Electricity Use 2005 to 2010
– year: 2007
  ident: bib0080
  article-title: Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency
– volume: 98
  start-page: 110
  year: 2016
  end-page: 128
  ident: bib0010
  article-title: Numerical investigation and parametric study for thermal and energy management enhancements in data centers’ buildings
  publication-title: Appl. Therm. Eng.
– volume: 33
  start-page: 597
  year: 2009
  end-page: 603
  ident: bib0165
  article-title: Heat transfer mechanisms in an impinging synthetic jet for a small jet-to-surface spacing
  publication-title: Exp. Therm. Fluid. Sci.
– volume: 36
  start-page: 2802
  year: 2011
  end-page: 2811
  ident: bib0190
  article-title: Heat pipe based cold energy storage systems for datacenter energy conservation
  publication-title: Energy
– volume: 76
  start-page: 155
  year: 2013
  ident: 10.1016/j.suscom.2018.05.002_bib0050
  article-title: A case study and critical assessment in calculating power usage effectiveness for a data centre
  publication-title: Energy Convers. Manag.
  doi: 10.1016/j.enconman.2013.07.035
– start-page: 249
  year: 2014
  ident: 10.1016/j.suscom.2018.05.002_bib0140
  article-title: Coordinating liquid and free air cooling with workload allocation for data center power minimization
– year: 2013
  ident: 10.1016/j.suscom.2018.05.002_bib0120
– ident: 10.1016/j.suscom.2018.05.002_bib0100
– volume: 31
  start-page: 622
  year: 2014
  ident: 10.1016/j.suscom.2018.05.002_bib0005
  article-title: A review of data center cooling technology, operating conditions and the corresponding low-grade waste heat recovery opportunities
  publication-title: Renew. Sustain. Energy Rev.
  doi: 10.1016/j.rser.2013.12.007
– issue: March
  year: 2011
  ident: 10.1016/j.suscom.2018.05.002_bib0125
  publication-title: ASHRAE J.
– volume: 4
  start-page: 200
  issue: no. 3
  year: 2014
  ident: 10.1016/j.suscom.2018.05.002_bib0220
  article-title: Cooling system analysis for a data center using liquid immersed servers
  publication-title: Int. J. Therm. Technol.
– volume: 90
  start-page: 937
  year: 2015
  ident: 10.1016/j.suscom.2018.05.002_bib0210
  article-title: Analysis on energy efficiency of an integrated heat pipe system in data centers
  publication-title: Appl. Therm. Eng.
  doi: 10.1016/j.applthermaleng.2015.07.078
– volume: 42
  start-page: 1726
  issue: 10
  year: 2010
  ident: 10.1016/j.suscom.2018.05.002_bib0250
  article-title: An experimental investigation on passive cooling system comprising phase change material and two-phase closed thermosyphon for telecom shelters in tropical and desert regions
  publication-title: Energy Build.
  doi: 10.1016/j.enbuild.2010.05.008
– volume: 60
  start-page: 1470
  year: 2016
  ident: 10.1016/j.suscom.2018.05.002_bib0240
  article-title: A review on phase change material (PCM) for sustainable passive cooling in building envelopes
  publication-title: Renew. Sustain. Energy Rev.
  doi: 10.1016/j.rser.2016.03.036
– volume: 43
  start-page: 237
  issue: no. 1
  year: 2012
  ident: 10.1016/j.suscom.2018.05.002_bib0145
  article-title: Aquasar: a hot water cooled data center with direct energy reuse
  publication-title: Energy
  doi: 10.1016/j.energy.2012.04.037
– volume: 41
  start-page: 36
  year: 2012
  ident: 10.1016/j.suscom.2018.05.002_bib0065
  article-title: On-chip two-phase cooling of datacenters: cooling system and energy recovery evaluation
  publication-title: Appl. Therm. Eng.
  doi: 10.1016/j.applthermaleng.2011.12.008
– volume: 50
  start-page: 1351
  issue: 1
  year: 2013
  ident: 10.1016/j.suscom.2018.05.002_bib0170
  article-title: Two-phase thermosyphon loop for cooling outdoor telecommunication equipments
  publication-title: Appl. Therm. Eng.
  doi: 10.1016/j.applthermaleng.2012.05.023
– volume: 2
  start-page: 1307
  issue: no. 8
  year: 2012
  ident: 10.1016/j.suscom.2018.05.002_bib0025
  article-title: Thermal management challenges in telecommunication systems and data centers
  publication-title: IEEE Trans. Componen. Packag. Manuf. Technol.
  doi: 10.1109/TCPMT.2012.2185797
– volume: 36
  start-page: 185
  issue: August
  year: 2018
  ident: 10.1016/j.suscom.2018.05.002_bib0265
  article-title: Design and economic analysis of liquid cooled data centres for waste heat recovery: a case study for an indoor swimming pool
  publication-title: Sustain. Cities Soc.
  doi: 10.1016/j.scs.2017.10.012
– volume: vol. 2
  start-page: 1
  year: 2009
  ident: 10.1016/j.suscom.2018.05.002_bib0070
– start-page: 1
  year: 2011
  ident: 10.1016/j.suscom.2018.05.002_bib0255
– volume: 16
  start-page: 2249
  issue: no. 4
  year: 2012
  ident: 10.1016/j.suscom.2018.05.002_bib0175
  article-title: A review of heat pipe systems for heat recovery and renewable energy applications
  publication-title: Renew. Sustain. Energy Rev.
  doi: 10.1016/j.rser.2012.01.038
– ident: 10.1016/j.suscom.2018.05.002_bib0180
– volume: 21
  start-page: 193
  issue: 2–3
  year: 2007
  ident: 10.1016/j.suscom.2018.05.002_bib0060
  article-title: Modeling of data center airflow and heat transfer: state of the art and future trends
  publication-title: Distrib. Parallel Databases
  doi: 10.1007/s10619-006-7007-3
– volume: 83
  start-page: 484
  year: 2015
  ident: 10.1016/j.suscom.2018.05.002_bib0135
  article-title: Cooling systems in data centers: state of art and emerging technologies
  publication-title: Energy Procedia
  doi: 10.1016/j.egypro.2015.12.168
– volume: vol. 59
  start-page: 198
  year: 2015
  ident: 10.1016/j.suscom.2018.05.002_bib0195
– volume: 98
  start-page: 110
  year: 2016
  ident: 10.1016/j.suscom.2018.05.002_bib0010
  article-title: Numerical investigation and parametric study for thermal and energy management enhancements in data centers’ buildings
  publication-title: Appl. Therm. Eng.
  doi: 10.1016/j.applthermaleng.2015.12.020
– volume: 48
  start-page: 5446
  issue: 25–26
  year: 2005
  ident: 10.1016/j.suscom.2018.05.002_bib0090
  article-title: An experimentally validated thermo-mechanical model for the prediction of thermal contact conductance
  publication-title: Int. J. Heat. Mass. Transf.
  doi: 10.1016/j.ijheatmasstransfer.2005.06.028
– volume: 26
  start-page: 1125
  issue: 11–12
  year: 2006
  ident: 10.1016/j.suscom.2018.05.002_bib0160
  article-title: Experimental study of the hydrodynamic and heat transfer of free liquid jet impinging a flat circular heated disk
  publication-title: Appl. Therm. Eng.
  doi: 10.1016/j.applthermaleng.2005.11.001
– volume: 33
  start-page: 597
  issue: no. 4
  year: 2009
  ident: 10.1016/j.suscom.2018.05.002_bib0165
  article-title: Heat transfer mechanisms in an impinging synthetic jet for a small jet-to-surface spacing
  publication-title: Exp. Therm. Fluid. Sci.
  doi: 10.1016/j.expthermflusci.2008.12.006
– ident: 10.1016/j.suscom.2018.05.002_bib0085
– volume: 57
  start-page: 126
  issue: 1–2
  year: 2013
  ident: 10.1016/j.suscom.2018.05.002_bib0185
  article-title: Mathematical model for heat transfer limitations of heat pipe
  publication-title: Math. Comput. Model.
  doi: 10.1016/j.mcm.2011.06.047
– year: 2010
  ident: 10.1016/j.suscom.2018.05.002_bib0030
– volume: 36
  start-page: 2802
  issue: no. 5
  year: 2011
  ident: 10.1016/j.suscom.2018.05.002_bib0190
  article-title: Heat pipe based cold energy storage systems for datacenter energy conservation
  publication-title: Energy
  doi: 10.1016/j.energy.2011.02.021
– volume: 95
  start-page: 297
  year: 2015
  ident: 10.1016/j.suscom.2018.05.002_bib0155
  article-title: The relationship among CPU utilization, temperature, and thermal power for waste heat utilization
  publication-title: Energy Convers. Manag.
  doi: 10.1016/j.enconman.2015.01.088
– volume: 14
  start-page: 620
  year: 2012
  ident: 10.1016/j.suscom.2018.05.002_bib0130
  article-title: The applied effect analysis of heat exchanger installed in a typical communication base station in Beijing of China
  publication-title: Energy Procedia
  doi: 10.1016/j.egypro.2011.12.985
– volume: 33
  start-page: 1
  year: 2008
  ident: 10.1016/j.suscom.2018.05.002_bib0215
  article-title: Dissipation thermique dans les systèmes électroniques
  publication-title: Tech. l’Ingénieur
– volume: 36
  start-page: 58
  issue: 1
  year: 2013
  ident: 10.1016/j.suscom.2018.05.002_bib0205
  article-title: Development of an integrated air conditioner with thermosyphon and the application in mobile phone base station
  publication-title: Int. J. Refrig.
  doi: 10.1016/j.ijrefrig.2012.09.012
– start-page: 1
  year: 2011
  ident: 10.1016/j.suscom.2018.05.002_bib0075
  article-title: Thermal guidelines for data processing environments – expanded data center
  publication-title: Data Process.
– volume: 30
  start-page: 1
  issue: no. 2
  year: 2008
  ident: 10.1016/j.suscom.2018.05.002_bib0035
  article-title: SMART 2020: enabling the low carbon economy in the information age
  publication-title: Group
– volume: 75
  start-page: 185
  year: 2015
  ident: 10.1016/j.suscom.2018.05.002_bib0200
  article-title: Integrated system of mechanical refrigeration and thermosyphon for free cooling of data centers
  publication-title: Appl. Therm. Eng.
  doi: 10.1016/j.applthermaleng.2014.09.060
– year: 2015
  ident: 10.1016/j.suscom.2018.05.002_bib0015
– start-page: 123
  year: 2010
  ident: 10.1016/j.suscom.2018.05.002_bib0230
  article-title: The merits of open bath immersion cooling of datacom equipment April
  publication-title: Annu. IEEE Semicond. Therm. Meas. Manag. Symp.
– year: 2007
  ident: 10.1016/j.suscom.2018.05.002_bib0260
– volume: 35
  start-page: 171
  year: 2014
  ident: 10.1016/j.suscom.2018.05.002_bib0105
  article-title: Free cooling of data centers: a review
  publication-title: Renew. Sustain. Energy Rev.
  doi: 10.1016/j.rser.2014.04.017
– volume: 53
  start-page: 2694
  issue: 13–14
  year: 2010
  ident: 10.1016/j.suscom.2018.05.002_bib0095
  article-title: A comprehensive flow regime map for microchannel flow boiling with quantitative transition criteria
  publication-title: Int. J. Heat. Mass. Transf.
  doi: 10.1016/j.ijheatmasstransfer.2010.02.039
– volume: 55
  start-page: 189
  year: 2012
  ident: 10.1016/j.suscom.2018.05.002_bib0020
  article-title: Viability of datacenter cooling systems for energy efficiency in temperate or subtropical regions : case study
  publication-title: Energy Build.
  doi: 10.1016/j.enbuild.2012.08.012
– year: 2007
  ident: 10.1016/j.suscom.2018.05.002_bib0040
– volume: 89
  start-page: 150
  issue: 1
  year: 2012
  ident: 10.1016/j.suscom.2018.05.002_bib0150
  article-title: Computational fluid dynamic investigation of liquid rack cooling in data centres
  publication-title: Appl. Energy
  doi: 10.1016/j.apenergy.2011.02.003
– year: 2010
  ident: 10.1016/j.suscom.2018.05.002_bib0110
– year: 2010
  ident: 10.1016/j.suscom.2018.05.002_bib0045
  article-title: Ere: a metric for measuring the benefit of reuse energy from a editor
  publication-title: Star
– volume: 6
  start-page: 17
  year: 2013
  ident: 10.1016/j.suscom.2018.05.002_bib0235
  article-title: Effect of climatic conditions on energy consumption in direct fresh-air container data centers 2013
  publication-title: 2013 Int. Green Comput. Conf. Proceedings, IGCC
– volume: 50
  start-page: 212
  issue: no. 7
  year: 2012
  ident: 10.1016/j.suscom.2018.05.002_bib0115
  article-title: Study of ventilation cooling technology for telecommunication base stations: control strategy and application strategy
  publication-title: Energy Build.
  doi: 10.1016/j.enbuild.2012.03.040
– volume: sUMMER
  start-page: 76
  issue: Lbnl
  year: 2006
  ident: 10.1016/j.suscom.2018.05.002_bib0055
  article-title: Best practices for data centers: lessons learned from benchmarking 22 data centers T
  publication-title: Aceee
– year: 2007
  ident: 10.1016/j.suscom.2018.05.002_bib0080
– volume: 117
  start-page: 95
  year: 2014
  ident: 10.1016/j.suscom.2018.05.002_bib0245
  article-title: A study on the use of phase change materials (PCMs) in combination with a natural cold source for space cooling in telecommunications base stations (TBSs) in China
  publication-title: Appl. Energy
  doi: 10.1016/j.apenergy.2013.12.010
– volume: 55
  start-page: 3379
  issue: 13–14
  year: 2012
  ident: 10.1016/j.suscom.2018.05.002_bib0225
  article-title: Novel heat transfer fluids for direct immersion phase change cooling of electronic systems
  publication-title: Int. J. Heat. Mass. Transf.
  doi: 10.1016/j.ijheatmasstransfer.2012.02.063
SSID ssj0000561934
Score 2.5419037
Snippet •Review of existing cooling technologies of data centers.•Analysis of energy consumption and energy savings of data centers.•Performance of various innovative...
SourceID hal
crossref
elsevier
SourceType Open Access Repository
Enrichment Source
Index Database
Publisher
StartPage 14
SubjectTerms Cooling technologies
Data center
Energy efficiency
Engineering Sciences
Mechanics
Thermal management
Thermics
Title A review of thermal management and innovative cooling strategies for data center
URI https://dx.doi.org/10.1016/j.suscom.2018.05.002
https://normandie-univ.hal.science/hal-02165699
Volume 19
hasFullText 1
inHoldings 1
isFullTextHit
isPrint
link http://utb.summon.serialssolutions.com/2.0.0/link/0/eLvHCXMwnV1LS-RAEG58XPbie_FNI3uNk6Tfx0GU8YmwCt6a7k737ojOiDN69LdblcegIAge0-lKQnVS9VXnqypC_qSkmHB5zDwPJuMOMJwplcyS91LwWFZOYYLz5ZUc3PKzO3E3R466XBikVba2v7HptbVuR3qtNntPw2HvbwnRimAK4g0IycHoYgY7V0jrO3wrZvssiJBN_XMZ52co0GXQ1TSvycsEaSPgB_Xhh_2VLzzU_P9ur7X2PScrZKkFjbTfPNcqmYujNbLcNWSg7fe5Tq77tElFoeNEEdk9gtTjjOBC3aiiw7YN6mukYYwde_7RybSrF0EBwlIkjVIkbcbnDXJ7cnxzNMjalglZYDyfZrwqTZl8lDKoXJZBVj4yWXjwVVw4iM1ClUKhKsRB3hmvHa-UCZrlTpRwjv0mC6PxKG4SWrFYSClEcEpzo5PxSTtRMC2T1tEUW4R1arKhrSeObS0ebEccu7eNci0q1-bCgnK3SDaTemrqaXwzX3UrYD-9FxZM_jeSB7Bgs5tgGe1B_8LiGOAagLHGvBbbP778DvmFRw3dbJcsTJ9f4h7gk6nfr1_AfbLYPz0fXL0D6dDlDw
linkProvider Elsevier
linkToHtml http://utb.summon.serialssolutions.com/2.0.0/link/0/eLvHCXMwnV1LT9wwEB7BcqCXPqBVoS-r6jVsEr-PK1QUyrKqBEjcLNuxyyLYRezC72e8cVZFqoTUq51JorEz843zzQzAjxgl5bYMhWNeF8wihtO1FEV0TnAW6tbKlOB8OhHNBft1yS834LDPhUm0ymz7O5u-stZ5ZJi1ObybTodnNUYrnEqMNzAkR6O7CVupOhUbwNbo-KSZrI9aEkjWq__LSaRIMn0S3YrptXhYJOYIukJ18NcRyz-c1OZVf9y6cj9Hb-F1xo1k1L3aO9gIsx140_dkIPkT3YXfI9Jlo5B5JAnc3aLU7ZrjQuysJdPcCfUxED9PTXv-kMWyLxlBEMWSxBslibcZ7t_DxdHP88OmyF0TCk9ZuSxYW-s6uiCEl6WovWhdoKJy6K4Ytxie-Tb6SrYJCjmrnbKsldorWlpe4xz9AIPZfBY-AmlpqITg3FupmFZRu6gsr6gSUamgqz2gvZqMzyXFU2eLG9Nzx65Np1yTlGtKblC5e1Cspe66khovXC_7FTDPtoZBq_-C5HdcsPVDUiXtZjQ2aQyhDSJZrR-r_f--_TfYbs5Px2Z8PDn5BK_STMc--wyD5f1D-IJwZem-5u34BMrr58A
openUrl ctx_ver=Z39.88-2004&ctx_enc=info%3Aofi%2Fenc%3AUTF-8&rfr_id=info%3Asid%2Fsummon.serialssolutions.com&rft_val_fmt=info%3Aofi%2Ffmt%3Akev%3Amtx%3Ajournal&rft.genre=article&rft.atitle=A+review+of+thermal+management+and+innovative+cooling+strategies+for+data+center&rft.jtitle=Sustainable+computing+informatics+and+systems&rft.au=Nadjahi%2C+Chayan&rft.au=Louahlia%2C+Hasna&rft.au=Lemasson%2C+St%C3%A9phane&rft.date=2018-09-01&rft.pub=Elsevier+Inc&rft.issn=2210-5379&rft.volume=19&rft.spage=14&rft.epage=28&rft_id=info:doi/10.1016%2Fj.suscom.2018.05.002&rft.externalDocID=S2210537917304067
thumbnail_l http://covers-cdn.summon.serialssolutions.com/index.aspx?isbn=/lc.gif&issn=2210-5379&client=summon
thumbnail_m http://covers-cdn.summon.serialssolutions.com/index.aspx?isbn=/mc.gif&issn=2210-5379&client=summon
thumbnail_s http://covers-cdn.summon.serialssolutions.com/index.aspx?isbn=/sc.gif&issn=2210-5379&client=summon