Mechanical Ventilation Control Based on Estimated occupancy using a Carbon Dioxide Sensor
Ventilation is an important aspect to maintain good indoor air quality in a building. However, excessive ventilation causing high energy consumption of the HVAC system. The ASHRAE Standard provides a guideline to set the ventilation rate that depends on the occupants' number and space. Thus, qu...
Saved in:
Published in | Teknik Vol. 41; no. 3; pp. 232 - 238 |
---|---|
Main Authors | , , , , |
Format | Journal Article |
Language | English |
Published |
Diponegoro University
28.11.2020
|
Subjects | |
Online Access | Get full text |
Cover
Loading…
Abstract | Ventilation is an important aspect to maintain good indoor air quality in a building. However, excessive ventilation causing high energy consumption of the HVAC system. The ASHRAE Standard provides a guideline to set the ventilation rate that depends on the occupants' number and space. Thus, quantification of the number of occupants is required to regulate the ventilation rate. In this study, the estimated number of occupants was estimated using a Bayesian MCMC method based on CO2 levels. The mass balance equation of the CO2 is used as a model for the calculation of Bayesian MCMC. The Bayesian method for estimating the occupants' number is tested in a 96,7 m3 office room equipped with a ventilation system. Thus the occupancy estimation and control of ventilation can be done in real-time. The test also includes conventional ventilation control based on CO2 levels directly without converting to the occupants' number. The ventilation rate based on the number of occupants at the present test chamber refers to ASHRAE 62.1. The test results show that ventilation controlled by the estimated number of occupants using the Bayesian method successfully conducted with ventilation rate per occupant closer to the ASHRAE 62.1 standard over conventional ventilation method |
---|---|
AbstractList | Ventilation is an important aspect to maintain good indoor air quality in a building. However, excessive ventilation causing high energy consumption of the HVAC system. The ASHRAE Standard provides a guideline to set the ventilation rate that depends on the occupants' number and space. Thus, quantification of the number of occupants is required to regulate the ventilation rate. In this study, the estimated number of occupants was estimated using a Bayesian MCMC method based on CO2 levels. The mass balance equation of the CO2 is used as a model for the calculation of Bayesian MCMC. The Bayesian method for estimating the occupants' number is tested in a 96,7 m3 office room equipped with a ventilation system. Thus the occupancy estimation and control of ventilation can be done in real-time. The test also includes conventional ventilation control based on CO2 levels directly without converting to the occupants' number. The ventilation rate based on the number of occupants at the present test chamber refers to ASHRAE 62.1. The test results show that ventilation controlled by the estimated number of occupants using the Bayesian method successfully conducted with ventilation rate per occupant closer to the ASHRAE 62.1 standard over conventional ventilation method |
Author | Arnas, Arnas Nasruddin, Nasruddin Rahman, Haolia Sukandi, Agus Lapisa, Remon |
Author_xml | – sequence: 1 givenname: Haolia orcidid: 0000-0002-3414-7225 surname: Rahman fullname: Rahman, Haolia organization: Department of Mechanical Engineering, Jakarta State Polytechnic – sequence: 2 givenname: Agus surname: Sukandi fullname: Sukandi, Agus organization: Department of Mechanical Engineering, Jakarta State Polytechnic – sequence: 3 givenname: Nasruddin surname: Nasruddin fullname: Nasruddin, Nasruddin organization: Faculty of Engineering, Padang State University – sequence: 4 givenname: Arnas surname: Arnas fullname: Arnas, Arnas organization: Faculty of Engineering, Padang State University – sequence: 5 givenname: Remon surname: Lapisa fullname: Lapisa, Remon organization: Faculty of Engineering, Padang State University |
BookMark | eNo9kMtOwzAQRS0EEqXwBWzyAyl-J15CKVAJxIKHxMqa-FEMwUZ2iujfE1rEajR3RldH5wjtxxQdQqcEzwhvCD4b3HsM77MvTgKbMcaJ3EMTyiWulSJqH01wK2hNpGoO0UkpocOcN5I2XE7Qy50zrxCDgb56dnEIPQwhxWqe4pBTX11AcbYag0UZwgcMv4sx60-IZlOtS4irCqo55G58uQzpO1hXPbhYUj5GBx764k7-5hQ9XS0e5zf17f31cn5-WxtCMK0tpb5jbec8ZUIKrkYwrDC3qhVONtQJ5RvOpeeN8I7RjhsQlrTj3UOHHZui5a7XJnjTn3mkzBudIOhtkPJKQx6C6Z1mnmDFLOBGWA4Yd5bTjmEhqASuRoApYrsuk1Mp2fn_PoL1VrbeydZb2Xorm_0At7l2FA |
ContentType | Journal Article |
DBID | AAYXX CITATION DOA |
DOI | 10.14710/teknik.v41i3.33416 |
DatabaseName | CrossRef Directory of Open Access Journals - May need to register for free articles |
DatabaseTitle | CrossRef |
DatabaseTitleList | CrossRef |
Database_xml | – sequence: 1 dbid: DOA name: Directory of Open Access Journals - May need to register for free articles url: https://www.doaj.org/ sourceTypes: Open Website |
DeliveryMethod | fulltext_linktorsrc |
Discipline | Engineering |
EISSN | 2460-9919 0852-1697 |
EndPage | 238 |
ExternalDocumentID | oai_doaj_org_article_3f1093da075d4a00bd42b305526a49f2 10_14710_teknik_v41i3_33416 |
GroupedDBID | 5VS AAYXX ADBBV ALMA_UNASSIGNED_HOLDINGS BCNDV CITATION GROUPED_DOAJ KQ8 KWQ RIG M~E |
ID | FETCH-LOGICAL-c1102-d22fb38bef23565496270904d985e672e59f7446f475fe32b4ca5d18d98fab0e3 |
IEDL.DBID | DOA |
ISSN | 0852-1697 |
IngestDate | Thu Jul 04 20:59:07 EDT 2024 Fri Aug 23 03:10:22 EDT 2024 |
IsDoiOpenAccess | true |
IsOpenAccess | true |
IsPeerReviewed | true |
IsScholarly | true |
Issue | 3 |
Language | English |
LinkModel | DirectLink |
MergedId | FETCHMERGED-LOGICAL-c1102-d22fb38bef23565496270904d985e672e59f7446f475fe32b4ca5d18d98fab0e3 |
ORCID | 0000-0002-3414-7225 |
OpenAccessLink | https://doaj.org/article/3f1093da075d4a00bd42b305526a49f2 |
PageCount | 7 |
ParticipantIDs | doaj_primary_oai_doaj_org_article_3f1093da075d4a00bd42b305526a49f2 crossref_primary_10_14710_teknik_v41i3_33416 |
PublicationCentury | 2000 |
PublicationDate | 2020-11-28 |
PublicationDateYYYYMMDD | 2020-11-28 |
PublicationDate_xml | – month: 11 year: 2020 text: 2020-11-28 day: 28 |
PublicationDecade | 2020 |
PublicationTitle | Teknik |
PublicationYear | 2020 |
Publisher | Diponegoro University |
Publisher_xml | – name: Diponegoro University |
SSID | ssib044762746 ssj0001764373 |
Score | 2.1823535 |
Snippet | Ventilation is an important aspect to maintain good indoor air quality in a building. However, excessive ventilation causing high energy consumption of the... |
SourceID | doaj crossref |
SourceType | Open Website Aggregation Database |
StartPage | 232 |
SubjectTerms | bayesian mcmc estimasi penghuni karbon dioksida kontrol ventilasi persamaan kesetimbangan massa |
Title | Mechanical Ventilation Control Based on Estimated occupancy using a Carbon Dioxide Sensor |
URI | https://doaj.org/article/3f1093da075d4a00bd42b305526a49f2 |
Volume | 41 |
hasFullText | 1 |
inHoldings | 1 |
isFullTextHit | |
isPrint | |
link | http://utb.summon.serialssolutions.com/2.0.0/link/0/eLvHCXMwrV3PS8MwFA6ykxdRVJy_yMGj2dI0aZKjmxtDmBedzFNpmkTGoJMxxZN_u--1VebJi5dC0xDK99L3g375HiFXmVdGl9GyoDVnsuCcuegD886gOluio8MDztP7bDKTd3M132r1hZywRh64Aa6fRhQ88gWENo9LOS-FQ5kqkRXSxsb7JmqrmIKdJKXGnjL1j0qjBEsyq1vJIXDGvL8Jy2qx7L3LZJH2UnDk2a-wtKXeX4eZ8T7Za_NDetO81wHZCdUheZ4GPKCLeNInpPc0BDY6bHjmdAChyFMYGMEHCyko3tTqweA5KTLbX2hBh8XawZTbxepj4QN9gPp1tT4is_HocThhbU8EVkKgFswLEV1qXIgihVxMYu8cbrn01qiQaRGUjRpKvCi1iiEVTpaF8omB57FwPKTHpFOtqnBCqDVZcBkP2osoXSmdTkrjbGllqQthQ5dcf0OSvzbSFzmWDIhg3iCY1wjmNYJdMkDYfqaibnU9ANbMW2vmf1nz9D8WOSO7AqviJGHCnJPOZv0WLiB12LjLepfAdfo5-gK-08D_ |
link.rule.ids | 315,786,790,870,2115,27957,27958 |
linkProvider | Directory of Open Access Journals |
openUrl | ctx_ver=Z39.88-2004&ctx_enc=info%3Aofi%2Fenc%3AUTF-8&rfr_id=info%3Asid%2Fsummon.serialssolutions.com&rft_val_fmt=info%3Aofi%2Ffmt%3Akev%3Amtx%3Ajournal&rft.genre=article&rft.atitle=Mechanical+Ventilation+Control+Based+on+Estimated+occupancy+using+a+Carbon+Dioxide+Sensor&rft.jtitle=Teknik&rft.au=Haolia+Rahman&rft.au=Agus+Sukandi&rft.au=Nasruddin+Nasruddin&rft.au=Arnas+Arnas&rft.date=2020-11-28&rft.pub=Diponegoro+University&rft.issn=0852-1697&rft.eissn=0852-1697&rft.volume=41&rft.issue=3&rft.spage=232&rft.epage=238&rft_id=info:doi/10.14710%2Fteknik.v41i3.33416&rft.externalDBID=DOA&rft.externalDocID=oai_doaj_org_article_3f1093da075d4a00bd42b305526a49f2 |
thumbnail_l | http://covers-cdn.summon.serialssolutions.com/index.aspx?isbn=/lc.gif&issn=0852-1697&client=summon |
thumbnail_m | http://covers-cdn.summon.serialssolutions.com/index.aspx?isbn=/mc.gif&issn=0852-1697&client=summon |
thumbnail_s | http://covers-cdn.summon.serialssolutions.com/index.aspx?isbn=/sc.gif&issn=0852-1697&client=summon |